Appendix c - vcb-x lon parameters, Pt-link ii interface, Pt-link ii lon – Orion System PT-Link II LON User Manual

Page 27: Technical guide 27

Advertising
background image

PT-Link II Interface

PT-Link II LON

®

Technical Guide

27

Appendix C - VCB-X LON Parameters

SNVTs for the VCB-X Controller

Binary Output SNVTs are SNVT_lev_disc

all other SNVTs are SNVT_count_inc_f

Parameter

Name

Object

Description

Limits

Bad or

Missing 12

Relay

Expansion

Board.

Mis12Rly

Binary
Output

The 12 Relay

Expansion

Board is con-

fi gured but not

detected.

Alarm

Group 1

AlmGrp1

Analog

Output

See Alarm

Group Bits on

page 38.

Alarm

Group 2

AlmGrp2

Analog

Output

See Alarm

Group Bits on

page 38.

Alarm

Group 3

AlmGrp3

Analog

Output

See Alarm

Group Bits on

page 38.

Alarm Status

AlmSts

Analog

Output

Indicates that

there is an

alarm.

0 = Off

1 = On

See Alarm

Group Bits on

page 38.

Application

Software

Version

AppVer

Analog

Output

Current version

of the software

in the unit.

Unit Mode

UnitMode

Analog

Output

See Unit Mode

Bits on page

38.

Building

Pressure

BuildPr

Analog

Output

Current value

of the building

pressure sensor.

Building

Pressure
Setpoint

RfPrSt

Analog

Input

Current

Building

Pressure

Setpoint.

-.20

.20

Building

Pressure

Control

Deadband

RfPrDb

Analog

Input

Value above

and below the

Building

Pressure

Setpoint where

no control

change occurs.

.01

0.1

CO

2

CO2

Analog

Output

Current CO

2

Level.

CO

2

Sensor

Calibration

Deadband

Offset

CO2Ost

Analog

Input

If the CO

2

Sensor is

reading

incorrectly, you

can use this

option to enter
an offset value

to adjust the

Sensor’s CO

2

reading.

-500

ppm

500

ppm

SNVTs for the VCB-X Controller

Binary Output SNVTs are SNVT_lev_disc

all other SNVTs are SNVT_count_inc_f

Parameter

Name

Object

Description

Limits

CO

2

Minimum

Setpoint

CO2MinLv

Analog

Input

This is the

threshold CO

2

level at which

the Economizer

Min Damper

Position

Setpoint will

begin to be

reset higher.

0

2000

CO

2

Maximum

Setpoint

CO2

MaxLv

Analog

Input

This is the CO

2

level at which

the Economizer

Min Damper
Position will

be reset to the

Economizer

Max Position
in High CO

2

.

In between the

Min and Max

CO

2

levels the

Economizer

Min Damper

Position will be

proportionally

reset between

the confi gured

Min Damper

Position and the
Max Position in

High CO

2

.

0

2000

Bad CO

2

Sensor

CO2Alm

Binary
Output

Failure of the

CO

2

Sensor.

Coil

Temperature

CoilTp

Analog

Output

Current coil
temperature

reading.

Coil

Temperature

Offset

ColTpOft

Analog

Input

If the Coil

Temperature

Sensor is

reading

incorrectly, use

this offset to

adjust the

Sensor’s

Temperature.

-100

100

Bad Coil Pres-

sure

Sensor

ColPrAlm

Binary
Output

Failure of the
Coil Pressure

Sensor. Will

shut unit down.

Coil Tempera-

ture Setpoint

CoilTpSt

Analog

Output

This is the

current

calculated Coil

Suction

Temperature

target during

Dehumidifi ca-

tion Mode.

NOTE:

When using Celsius scaling, all temperature values will
need to be divided by 10 by the BMS to properly read the
status and setpoint values, e.g., a value of 200º C needs
to be divided by 10 for an actual value of 20º C.

Advertising