Use the standard EIA/TIA color code for "CROSS OVER CABLE" as shown.

It is

the same as a standard Cat 5 patch cabling. The outer cable jacket should

Be "Orange" in color. This is

a straight thru pin 1 to pin 1 cable.

not

not

1
2
3
4
5
6

RJ-45 Connector as viewed
from the bottom side

8
7
6
5
4
3

RJ-45 Connector as viewed
from the bottom side

Brown/White
White/Brown
Orange/White
White/Blue
Blue/White
White/Orange

White/Orange
Orange/White
White/Green
Blue/White
White/Blue
Green/White

Figure 25: RJ-45 8P8C Cable for WattMaster Cross Over Networking - WattMaster Part #HZ000136

Appendix A & B

External Interface Files (XIF Files)

At start-up the PT-Link II LON creates an external interface fi le (XIF)
called fServer.xif based on the information contained in the PT-Link
II LON’s confi guration fi le (confi g.csv). The PT-Link II LON’s con-
fi guration can be changed by uploading and editing the confi g.csv
fi le; therefore, the XIF fi le must be obtained by uploading it from the
PT-Link II LON.

The recommended procedure for obtaining the XIF fi le for the PT-Link
II LON is to upload it. Remember that this XIF fi le will change when-
ever the confi guration fi le has been changed and downloaded and the
PT-Link II LON restarted. The following are the steps to extract the
external interface fi le (XIF) from the PT-Link II LON:

1.) Start RUINET application.

2.) Select Fieldserver option

<1>

(this step may be skipped

when application auto-detects PT Link).

3.) From

the

RUINET Main Menu, type <A> – Data Array

Overview.

4.) You should see 2 array items that are labeled wattmstr-

dump and wattmstr-stats. Ignore these.

5.) You should see 2 additional arrays for the controller
connected.

Example: DA_C162_I0 and DA_C162_I0b.

5.1.) The “b” at the end of the Data Array Name indicates

that it is a mirror array. You can ignore these.

5.2) Verify that your controller is visible or the XIF will not

be generated.

6.) After connection has been verifi ed, you can

now exit to the RUINET Main Menu by pressing

<ESC>

.

7.) Type

<U>

– Upload Confi guration.

8.) Type

<O>

to select other fi les.

9.) If

prompted,

press any key to continue.

10.) Type

<R>

– Remote Filename.

11.) Type

<fserver.xif>

.

12. You should now see the name fserver.xif in the column to
the

right.

13. Type

<U>

to upload the XIF fi le.

14. Once

fi nished, you will have an .xif fi le available in the

same directory as the RUINET executable fi le you were

running

from.

WARNING: