Vcm controller wiring, Component & system wiring 32, Vcm controller main board wiring – Orion System VCM Component User Manual

Page 32: All comm loop wiring is straight thru, T to t, r to r & shld to shld, Ovcm-mainwire-1a.cdr, Line voltage

Advertising
background image

Component & System Wiring

32

VCM Controller Wiring

FILENAME

DATE:

B. Crews

DESCRIPTION:

PAGE

DRAWN BY:

JOB NAME

OVCM-MainWire-1A.CDR

1 of 1

02/28/06

Line Voltage

All Comm Loop Wiring Is

Straight Thru

24VAC

GND

Local Loop

RS-485

9600 Baud

See Individual

Component Wiring

Diagrams For Detailed

Wiring Of Analog Inputs

And Outputs

For Stand Alone Applications,

Connect To System Manager. For Network

Applications Connect To Next Controller And/Or

MiniLink PD On Local Loop.

G - Fan ON/OFF Only

R - 24VAC

Relay Output Dry Contacts
R2 Thru R5 May Be User Configured
For The Following:

1 - Heating Stages
2 - Cooling Stages
3 - Warm-up Mode Command (VAV Boxes)
4 - Reversing Valve (Air To Air Heat Pumps)
5 - Reheat Control (Dehumidification)
6 - Exhaust Fan Interlock
7 - Preheater For Low Ambient Protection
8 - Alarm
9 - Override
10 - Occupied
11 - OA Damper

Note: A Total Of 20 Relays Are Available By
Adding Relay Expansion Boards. All Expansion
Board Relay Outputs Are User Configurable As
Listed Above.

OE271

Static Pressure

Transducer

Splice If Req’d

Connect To
Expansion Board
Base (When Used)

RL

Y1

D1

D2

D3

D4

D5

RAM

C3

C2

U6

PHILIPS

CX6

C1

CX2

U2

PAL

CX4

U4

TUC-5R PLUS

YS101816 REV. 2

V1

V2

V3

V5

V4

TB2

4

NETWORK

TOKEN

16

32

8

SW1

ADD

2

1

ADDRESS

V6

POWER

GND

24VAC

L1

D16

R6

C9

SC1

R1

1

U1

1

MC34064A

D13

C16

9936

VR2

TB4

R27

C13

R10

VR1

C19

C18

NE5090NPB3192

0PS

U8

CX8

U9

X1

R7

D10

R13

D12

C7

CX10

U10

CX12

U12

U14

CX14

PJ3

PJ2

PJ1

EXPANSION

PRESSURE
SENSOR

C17

D15

R26

C20

R25

R24

R22

U15

CX13

U13

C15

R19

R15

C14

D18

D17

PU1

PU2

PU3

PU4

PU5

PU7

D6

D7

D8

D9

D11

D14

C12

C10

0-5

VDC

0-1

VDC

JP1

C1

1

X2

GND

TB3

INPUTS

GND

GND

+VDC

AIN1

AIN2

AIN3

AIN4

AIN5

AOUT1

AOUT2

AIN7

RN4

1

RN5

RS-485

CX5

U5

R

TB1

SHLD

T

COMM

COMM

RN3

1

RN1

U1

CX1

1

LD6

COMM

PWR

LD7

LED1

LED2

LD9

LD8

R1

U7

RV1
VREF ADJ

R28

+VREF

5.11V

TEST POINT

EWDOG

D19

RN2

1

COM1-3

COM4-5

R5

R4

R3

R2

R1

RL

Y2

RL

Y3

RL

Y4

RL

Y5

CX15

(1 MEG)

HH

P1

C21

CX3

EPROM

U3

Warning:
24 VAC Must Be Connected So That All Ground
Wires Remain Common. Failure To Do So Will
Result In Damage To The Controllers.

T to T, R to R & SHLD to SHLD

Size Transformer For
Correct Total Load.
VCM Controller = 8 VA
Power Consumption. If
Economizer Option Is Used
The Economizer Actuator
VA load Must Also Be
Considered When Sizing
The Transformer.

OE331-21-VCM

VCM Controller Board

Note:
All Relay Outputs Are Normally Open
And Rated For 24 VAC Power Only.
2 Amp Maximum Load.

VCM Controller

Main Board Wiring

Notes:
1.) Connect FRP Tubing To The High Pressure
Port (Bottom Tube) Of The Staic Pressure
Transducer And Route The Tubing To The
Static Pressure Pickup Probe Location. Leave
The Port Marked “LO” Open To Atmosphere.

2.) The Static Pressure Pickup Probe Should
Ideally Be Mounted With The Probe Pointing
At A 90 Degree Angle To The Supply Air Flow
Direction. It Should Be Located In A Straight
Section Of The Supply Air Duct At A Distance
From The Unit Discharge That Is Approximately
Equal To 2/3 The Length Of The Longest
Supply Air Duct Run. Also Ideally The Probe
Should Be Located Not Less Than 3 Duct
Diameters Downstream And 2 Duct Diameters
Upstream Of Any Elbow Or Takeoff In The
Ductwork.

Advertising