background image

Component & System Wiring

38

FILENAME

DATE:

B. Crews

DESCRIPTION:

PAGE

DRAWN BY:

JOB NAME

OVCM-SuctPress-WO-DSC-1A.CDR

1 of 1

03/06/06

VCM Controller Wiring Detail

Suction Pressure Transducer W/O DSC

WARNING!!
Observe Polarity! All boards must be wired with GND-to-GND and 24VAC-to-24VAC. Failure to observe polarity will result
in damage to one or more of the boards. Expansion Boards must be wired in such a way that power to both the
expansion boards and the controller are always powered together. Loss of power to the expansion board will cause the
controller to become inoperative until power is restored to the expansion board.

BK

RD

WH

Transducer Cable

With Built-In Signal

Conditioner

OE331-21-VCM

VCM Controller Board

OE275-01-NDC

Suction Pressure Transducer

(250 PSIG)

With Signal Conditioner

AIN5

GND

+VDC

Pullup Resistor PU5
Must Be Removed

Note:
Use This Diagram Only For Applications Without
Copeland Digital Scroll Compressors. For Applications
With Copeland Digital Scroll Compressors See The
Wiring Detail For Suction Pressure Transducers With
Copeland Digital Scroll Compressors.

Suction Pressure Transducer Without Digital Compressor - Wiring