Component & System Wiring

48

FILENAME

DATE:

B. Crews

DESCRIPTION:

PAGE

DRAWN BY:

JOB NAME

OVCM-ModHeat-Cool-Wr1A..CDR

1 of 1

03/06/06

VCM Controller Wiring Detail

Modulating Heating and Cooling

24

V

A

C

GND

10 VA Minimum Power Required For

Each 2 Slot Expansion Base Board.

20 VA Minimum Power Required For

Each 4 Slot Expansion Base Board

R20

C8

TB2

D3

PWR LD1

24V
AC-IN

GND

GND

TB1

PJ2

+24VDC-OUT

R17

PJ1

R15

Connect To VCM Controller

Connect To Next

Expansion Board

(When Used)

GND

AOUT2

AOUT1

OE355

-

4

Analog

Output

Board

OE352 or OE353 Expansion Base Board

WARNING!!
Observe Polarity! All boards must be wired with GND-to-GND and 24VAC-
to-24VAC. Failure to observe polarity will result in damage to one or more
of the boards. Expansion Boards must be wired in such a way that power to
both the expansion boards and the controller are always powered together.
Loss of power to the expansion board will cause the controller to become
inoperative until power is restored to the expansion board.

GND

AOUT1

YS101786

4 AOUT MOD. I/O BD.

CX1

U1

Q1

LM358

R2

U2

R9

D1

R6

D2

R7

D4

D3

R8

TB1

CX2

C3

C1

P1

RV
1

R1

C4

U3

C2

LM358

CX3

AOUT2

AOUT3

AOUT4

Q2

R3

Q4

Q3

R4

R5

+

+

Modulating Heating Device

(By Others)

Modulating Cooling Device

(By Others)

_

_

GND

GND

0-10 VDC or 2-10 VDC

(Configurable)

0-10 VDC, 2-10 VDC or 1.5-5.0 VDC

(Configurable)

The Cooling Device Used Can
Be A Modulating Chilled Water
Valve or A Digital Scroll
Compressor. If Using A Digital
Scroll Compressor Please See
Digital Scroll Detailed Wiring
Information In This Manual.

The Cooling Device Used Can Be A
Modulating Chilled Water Valve or A Digital
Scroll Compressor. If Using A Digital Scroll
Compressor Please See Digital Scroll
Detailed Wiring Information In This Manual.

The Heating Device Used Can Be A
Modulating Hot Water Valve, Modulating
Steam Valve or SCR Controlled Electric
Heating Coil.

Note:
1.)The Modulating Cooling Device Used Must Be Capable Of
Accepting Either A 0-10 VDC, 2-10 VDC Or 1.5-5.0 VDC Input.

The AOUT1

Output Voltage Is User Configurable For These Voltages.

The AOUT2 Output Voltage Is User Configurable For These Voltages
The Modulating Heating Devices Used Must Be Capable Of
Accepting Either A 0-10 VDC Or 2-10 VDC Input.

These

Voltage Outputs Must Be Configured When You are Setting-up The
VCM Controller(s) Operating Parameters. See the VCM Controller
Operator Interfaces Technical Guide For Complete Controller
Programming and Configuration Information.

2.) Each Modulating Heating Or Cooling Device Used On The VCM
Controller Must Have (1) Relay Output Configured For Each Device
Used, In Order To Enable The Modulating Heating And/Or Cooling
Device's Sequence. This Relay Output Must Be Configured When
Setting-up The VCM Controller Operating Parameters. See the VCM
Controller Operator Interfaces Technical Guide For Complete
Controller Programming and Configuration Information.

Modulating Heating & Cooling Wiring