Building pressure sensor, actuator & vfd wiring, Component & system wiring 45 – Orion System VCM Component User Manual

Page 45

Advertising
background image

Component & System Wiring

45

FILENAME

DATE:

B. Crews

DESCRIPTION:

PAGE

DRAWN BY:

JOB NAME

OVCM-BPS-BPA-BPVFD-Wr-1A.CDR

1 of 1

03/06/06

VCM Controller Wiring Detail

Building Pressure Sensor, Actuator & VFD Wiring

R20

C8

TB2

D3

PWR LD1

24V
AC-IN

GND

GND

TB1

PJ2

+24VDC-OUT

R17

PJ1

R15

Modular Cable

Connect To VCM Controller

Modular Cable

Connect To Next Expansion Board

(When Used)

24

V

A

C

GND

OE352 2 Slot Or OE353 - 4 Slot Expansion Board

As Required - OE353 Is Shown

10 VA Minimum Power Required For

Each OE352 - 2 Slot Expansion Base Board.

20 VA Minimum Power Required For

Each OE353 - 4 Slot Expansion Base Board

WARNING!!
Observe Polarity! All boards must be wired with GND-to-GND and 24VAC-to-24VAC. Failure to observe polarity will result
in damage to one or more of the boards. Expansion Boards must be wired in such a way that power to both the
expansion boards and the controller are always powered together. Loss of power to the expansion board will cause the
controller to become inoperative until power is restored to the expansion board.

JO3

JO4

JO2

JO1

CX2

R10

AOUT1

AIN4

TB1

GND

AIN2
AIN3

AIN1

PU4

U2

D5

Q1

R8

R9

LM358

C5

C1

R7

R6

R5

PU3

C4

C3

C2

PU2

PU1

4 ANALOG IN MOD. I/O BD.

R3

YS101784

D4

R4

D3

D1

D2

R2

R1

CX1

U1

P1

OE354

-

4

Analog

Input

-

1

Analog

Output

Board

AOUT1

GND

AIN4

+

-

LOW

HIGH

COM

COM

OUT

EXC

+

+

+

Plastic Tubing To Building
Pressure Sensing Locations

Building Pressure

Relief FAN VFD

(0-10 VDC)

Orion - OE258 Building Pressure

Transducer

Building Pressure Control

Damper Actuator

(0-10 VDC)

Belimo Actuator Wiring

Shown. Consult Factory

For Other Manufacturers

Wiring Instructions

Either The Building Pressure

Control Damper Actuator (Used for
Reverse Building Pressure Control

Applications)Or The Building

Pressure Relief Fan VFD Control

Can Be Used, Not Both.

Y1

3

+

2

COM 1

Building Pressure Sensor, Actuator & VFD Wiring