Gbd controller - co2 applications wiring (cont’d), Component & system wiring 76, Gbd device – Orion System VCM Component User Manual

Page 76

Advertising
background image

Component & System Wiring

76

FILENAME

DATE:

B. CREWS

DESCRIPTION:

PAGE

DRAWN BY:

JOB NAME

FILENAME

JOB NAME

2 of 5

OE331-21- AVG

GBD Device Wiring

OE255 or OE256
CO Sensor
(4-20mA Signal)

2

1. - Not Used

2. - Not Used

4. Relay Common
5. Relay Norm Closed

6. 4-20mA Output

3. Relay Norm Open

7. Signal Ground

8. 0-10V Output

Pin Designations

Pin Designations

1. AC+/DC+

2. AC/GND

Line

V

olt

age

Warning

:

24 VAC Must Be Connected So That All Ground
Wires Remain Common. Failure To Do So Will
Result In Damage To The Controllers.

GBD Device

24VAC

24V

A

C

24VAC

GND

GND

GND

250 Ohm-1%
Resistor Supplied
With CO Sensor(s)
Must Be Wired
As Shown For
Each Sensor Used

2

Up to (6) CO Sensors Can
Be Used On The GBD.

AIN2, AIN3, AIN4,

2

They Can Be Wired
To AIN1,

AIN5 And AIN7 As

Desired. Only 4-20mA
CO Sensor(s) May Be
Used.

2

POWER

VR2

TB4

VR1

PJ3

PJ2

PJ1

EXPANSION

PRESSURE

T'STAT

SENSOR

C17

D15

C20

D17

D6

D7

D8

D9

D11

D14

C12

C10

0-5

VDC

0-1

VDC

JP1

X2

TB3

INPUTS

+VDC

AOUT1

AOUT2

AIN7

AIN5

AIN4

AIN3

AIN2

AIN1

RN5

C4

CX15

The Pullup Resistor For The Analog
Input That Each CO Sensor Is Connected
To Must Be Removed For Proper
Operation Of The GBD Device.

2

PU1

PU2

PU3

PU4

PU5

GND

GND

PU7

GND

OE331-21-AVG

GBD Device Wiring

When Used For CO Applications

2

2.) 24 VAC Must Be Connected

So That All Ground Wires
Remain Common.

Notes:

4.) All Wiring To Be In Accordance

With Local And National Electrical
Codes And Specifications.

3.) Set-up, Programming And

Monitoring Of The GBD Device
Requires The Use Of A Personal
Computer And Prism Software.

1.) The GBD Can Either Be Used

With CO2 Sensors Or Space
Temperature Sensors But Not
Both On The Same GBD Device.
Up to 2 GBD Devices Can Be
Located On Each Local Loop.

24 VAC Transformer

20VA Minimum

Typical Wiring
Shown For Input

AIN3. Wiring For

Other Inputs Is
Identical.

10/07/05

OE331-21-AVG-GBD-Wire1A.CDR

GBD Controller - CO2 Applications Wiring (Cont’d)