Component & System Wiring

44

FILENAME

DATE:

B. Crews

DESCRIPTION:

PAGE

DRAWN BY:

JOB NAME

OVCM-Spc-HumSensorWr-1A.CDR

1 of 1

03/06/06

VCM Controller Wiring Detail

Space Humidity Sensor Wiring

24

V

A

C

GND

10 VA Minimum Power Required For

Each 2 Slot Expansion Base Board.

20 VA Minimum Power Required For

Each 4 Slot Expansion Base Board

R20

C8

TB2

D3

PWR LD1

24V
AC-IN

GND

GND

TB1

PJ2

+24VDC-OUT

R17

PJ1

R15

Connect To VCM Controller

Connect To Next Expansion Base Board

(When Used)

OE354

-

4

Analog

Input

-

1

Analog

Output

Board

GND

AIN2

0-5 VDC Input

Jumpers Must Be Set

as Shown For

Correct

O-5 VDC Operation

1 & 3 Are Off
2 & 4 Are On

Jumpers Must Be

Set as Shown For

Normal

Vo

Zero

Span

Gnd

Vi

n

Io

4

4

4

4

5

5

6

6

ON

ON

ON

ON

3

3

3

3

2

2

2

2

1

1

1

1

JO3

JO4

JO2

JO1

CX2

R10

AOUT1

AIN4

TB1

GND

AIN2
AIN3

AIN1

PU4

U2

D5

Q1

R8

R9

LM358

C5

C1

R7

R6

R5

PU3

C4

C3

C2

PU2

PU1

4 ANALOG IN MOD. I/O BD.

R3

YS101784

D4

R4

D3

D1

D2

R2

R1

CX1

U1

P1

Pullup Resistor PU2 Must
Be Removed As Shown

Jumper J02 Must
Be Removed As Shown

OE352 or OE353 Expansion Base Board

OE265-11

Space Humidity Sensor

WARNING!!
Observe Polarity! All boards must be wired with
GND-to-GND and 24VAC-to-24VAC. Failure to
observe polarity will result in damage to one or
more of the boards. Expansion Boards must be
wired in such a way that power to both the
expansion boards and the controller are always

Indoor Air Humidity Sensor Wiring

Advertising