Component & System Wiring

49

FILENAME

DATE:

B. Crews

DESCRIPTION:

PAGE

DRAWN BY:

JOB NAME

OVCM-RA-Byp-Wr1A.CDR

1 of 1

03/06/06

VCM Controller Wiring Detail

Return Air Bypass

24

V

A

C

GND

10 VA Minimum Power Required For

Each 2 Slot Expansion Base Board.

20 VA Minimum Power Required For

Each 4 Slot Expansion Base Board

R20

C8

TB2

D3

PWR LD1

24V
AC-IN

GND

GND

TB1

PJ2

+24VDC-OUT

R17

PJ1

R15

Connect To VCM Controller

Connect To Next

Expansion Board

(When Used)

GND

AOUT4

AOUT3

2-10 VDC

2-10 VDC

OE355

-

4

Analog

Output

Board

OE352 or OE353 Expansion Base Board

WARNING!!
Observe Polarity! All boards must be wired with GND-to-GND and 24VAC-
to-24VAC. Failure to observe polarity will result in damage to one or more
of the boards. Expansion Boards must be wired in such a way that power to
both the expansion boards and the controller are always powered together.
Loss of power to the expansion board will cause the controller to become
inoperative until power is restored to the expansion board.

GND

AOUT1

YS101786

4 AOUT MOD. I/O BD.

CX1

U1

Q1

LM358

R2

U2

R9

D1

R6

D2

R7

D4

D3

R8

TB1

CX2

C3

C1

P1

RV
1

R1

C4

U3

C2

LM358

CX3

AOUT2

AOUT3

AOUT4

Q2

R3

Q4

Q3

R4

R5

Return Air Bypass

Damper Actuator

(2-10 VDC)

Return Air

Damper Actuator

(2-10 VDC)

Belimo Actuator

Wiring Shown.

Consult Factory For

Other Manufacturers

Wiring Instructions

Y1

3

Y1

3

+

2

+

2

COM 1

COM 1

Return Air Bypass Wiring