Component & System Wiring

34

VCM Controller Wiring Detail

OA, SA and RA Temperature Sensors

GND

INPUTS

GND

AOUT1
AOUT2

GND

+VDC

AIN1
AIN2
AIN3
AIN4
AIN5

AIN7

Mount In HVAC

Unit Supply

Air Duct

Mount In HVAC

Unit Return

Air Duct

OE331-21-VCM

VCM Controller Board

OE231

Supply Air Temperature Sensor

(See Caution Note Below Regarding

Connection Location)

OE231

Return Air Temperature Sensor

FILENAME

DATE:

B. Crews

DESCRIPTION:

PAGE

DRAWN BY:

JOB NAME

OVCM-OA-SA-RASnsr-Wr-1A.CDR

1 of 2

Caution:

If your HVAC unit is supplied with the MODGAS II controller with or without an MHGRV II controller, the Supply Air Temperature

Sensor must always be wired to the MODGAS II controller. If your HVAC unit is supplied with only the MHGRV II controller, the

Supply Air Temperature Sensor must be connected to the MHGRV II controller.

If you have either of these controllers on your HVAC unit and connect a Supply Air Temperature Sensor to the VCM controller,

your controls will not function correctly. Only one Supply Air Temperature Sensor can be used on each HVAC unit.

See the Miscellaneous Diagrams & Technical

Information section in the back of this manual for detailed connection diagrams when using MODGAS II or MHGRV II controllers.

02/28/06

OE250

Outdoor Air

Temperature Sensor

Make Splice Connections
Inside Sensor Enclosure
As Shown. Seal All Conduit
Fittings With Silicone Sealant.

Mount Sensor Outdoors

In Shaded Protected

Area & In Upright

Position As Shown

Outdoor Air, Return Air & Supply Air Temperature Sensor Wiring