Component & system wiring 39 – Orion System VCM Component User Manual

Page 39

Advertising
background image

Component & System Wiring

39

FILENAME

DATE:

B. Crews

DESCRIPTION:

PAGE

DRAWN BY:

JOB NAME

OVCM-SuctPressW-DSC-1A.CDR

1 of 1

03/06/06

VCM Controller Wiring Detail

Suction Pressure Transducer W/O DSC

WARNING!!
Observe Polarity! All boards must be wired with GND-to-GND and 24VAC-to-24VAC. Failure to observe polarity will result
in damage to one or more of the boards. Expansion Boards must be wired in such a way that power to both the
expansion boards and the controller are always powered together. Loss of power to the expansion board will cause the
controller to become inoperative until power is restored to the expansion board.

OE355

-

4

Analog

Output

Board

GND

AOUT2

1.5 - 5 VDC

24

V

A

C

GND

OE352 or OE353 Expansion Base Board

OE331-21-VCM

VCM Controller Board

10 VA Minimum Power Required For

Each 2 Slot Expansion Base Board.

20 VA Minimum Power Required For

Each 4 Slot Expansion Base Board

GND

INPUTS

GND

AOUT1

AOUT2

GND

+VDC

AIN1

AIN2

AIN3

AIN4

AIN5

AIN7

Copeland Digital

Compressor

Controller

P4

RD

WH

BK

P3

P2

P1

SHLD

EXC

OUT

COM

P5

P6

C1

C2

R20

C8

TB2

D3

PWR LD1

24V
AC-IN

GND

GND

TB1

PJ2

+24VDC-OUT

R17

PJ1

R15

Connect To VCM Controller

Connect To

Next Expansion Base Board

(When Used)

OE275-01-NDC

Suction Pressure

Transducer

(250 PSIG)

Note:
Use This Diagram Only For Applications With
Copeland Digital Scroll Compressors. For Applications
Without Copeland Digital Scroll Compressors See The
Wiring Detail For Suction Pressure Transducers Without
Copeland Digital Scroll Compressors.

Suction Pressure Transducer With Digital Compressor - Wiring

Advertising