background image

Component & System Wiring

37

FILENAME

DATE:

B. Crews

DESCRIPTION:

PAGE

DRAWN BY:

JOB NAME

OVCM-ZoneByp-SFVFD-Wr1A.CDR

1 of 1

03/06/06

VCM Controller Wiring Detail

Supply Fan VFD or Bypass Damper Actuator

Bypass Damper Actuator

(Belimo Actuator Shown)

0-10 VDC

24 VAC Power Source

Sized For Actuator VA Load

GND

24 VAC

Y1 3

Y1 3

+ 2

+ 2

COM -

1

COM -

1

GND

INPUTS

GND

AOUT1
AOUT2

GND

+VDC

AIN1
AIN2
AIN3
AIN4
AIN5

AIN7

OE331-21-VCM

VCM Controller Board

Belimo Actuator Wiring

Shown. Consult Factory For

Other Manufacturers Wiring

Instructions

+

Supply Fan Variable Frequency Drive

(By Others)

_

VFD 0-10VDC Input

GND

Caution:
The VFD Unit Must Be Configured
For 0-10 VDC Input. The Input
Resistance At The VFD Must Not
Be Less Than 1000 Ohms When
Measured At The VFD Terminals
With All Input Wires Removed.

Note:
Either The Supply Fan
Variable Frequency Drive
Option Or The Bypass
Damper Actuator Option May
Be Connected To AOUT2 On
The VCM Controller. Only
One Option Is Allowed, Not
Both.

Supply Fan VFD & Bypass Damper Actuator Wiring