Component & system wiring 36 – Orion System VCM Component User Manual

Page 36

Advertising
background image

Component & System Wiring

36

FILENAME

DATE:

B. Crews

DESCRIPTION:

PAGE

DRAWN BY:

JOB NAME

OVCM-Spc-RemSA-Rst-Wr1A.CDR

1 of 1

03/06/06

VCM Controller Wiring Detail

Space Sensor & Remote Supply Air Temp. Reset

Remote Supply Air

Temperature Reset Signal

(By Others)

AIN7

GND

0-5 VDC or 0-10 VDC Signal

GND

Pullup Resistor PU7 Must Be
Removed When Using The
Remote Supply Air Temperature

Signal Input

Reset

Note:
Either The Slide Offset Option For The Space
Temperature Sensor Or The Remote Supply Air
Temperature Reset Signal Option (by Others) May Be
Connected To AIN7 On The VCM Controller. Only
One Option Is Allowed, Not Both.

Note:
When Using 0-10 VDC For The
Remote Signal Source Must
Have (2) 10kOhm Resistors
Wired As Shown. When Using 0-
5 VDC For The Remote Signal
These Resistors are Not
Required And The Signal Can Be
Wired Directly To AIN7 and GND.

Note:
When Using 0-10 VDC For The
Remote Signal Source Must
Have (2) 10kOhm Resistors
Wired As Shown. When Using 0-
5 VDC For The Remote Signal
These Resistors are Not
Required And The Signal Can Be
Wired Directly To AIN7 and GND.

OE210,OE211, OE212 or OE213

Space Temperature Sensor

OVR

OVR

AUX

GND

TEMP

10kOhm

10kOhm

Space Temperature Sensor & Remote Supply Air Reset Wiring