Co2 sensor wiring, Component & system wiring 46, Vcm controller wiring detail – Orion System VCM Component User Manual

Page 46

Advertising
background image

Component & System Wiring

46

FILENAME

DATE:

B. Crews

DESCRIPTION:

PAGE

DRAWN BY:

JOB NAME

OVCM-CO2-SensorWr-1A.CDR

1 of 1

03/06/06

VCM Controller Wiring Detail

CO Sensor Wiring

2

24

V

A

C

GND

10 VA Minimum Power Required For

Each 2 Slot Expansion Base Board.

20 VA Minimum Power Required For

Each 4 Slot Expansion Base Board

R20

C8

TB2

D3

PWR LD1

24V
AC-IN

GND

GND

TB1

PJ2

+24VDC-OUT

R17

PJ1

R15

Connect To VCM Controller

Connect To Nex

Expansion Base Board

(When Used)

OE354

-

4

Analog

Input

-1

Analog

Output

Board

GND

AIN3

0-10 VDC Input

JO3

JO4

JO2

JO1

CX2

R10

AOUT1

AIN4

TB1

GND

AIN2
AIN3

AIN1

PU4

U2

D5

Q1

R8

R9

LM358

C5

C1

R7

R6

R5

PU3

C4

C3

C2

PU2

PU1

4 ANALOG IN MOD. I/O BD.

R3

PCF8591P

YS101784

D4

R4

D3

D1

D2

R2

R1

CX1

U1

P1

OE255 or OE256

CO Sensor

(0-10VDC Signal)

2

1.

-

Not

Used

2.

-

Not

Used

4.

Relay

Common

5.

Relay

Norm

Closed

6.

4-20mA

Output

3.

Relay

Norm

Open

7.
Signal

Ground

8.

0-10V

Output

Pin

Designations

Pin

Designations

1.

AC+/DC+

2.

AC/GND

Pullup Resistor PU3 Must
Be Removed As Shown

Jumper J03 Must
Be In Place As Shown

OE352 or OE353 Expansion Base Board

WARNING!!
Observe Polarity! All boards must be wired with GND-to-GND and 24VAC-to-
24VAC. Failure to observe polarity will result in damage to one or more of the
boards. Expansion Boards must be wired in such a way that power to both the
expansion boards and the controller are always powered together. Loss of power
to the expansion board will cause the controller to become inoperative until
power is restored to the expansion board.

CO2 Sensor Wiring