Component & system wiring 84, Philips, When used with orion vcm controller – Orion System VCM Component User Manual

Page 84: Aaon modgas ii wiring 1, Filename date: b. crews description: page drawn by, Line gnd 24vac, O-modgasii-vcm-wr1.cdr, Mount in unit supply air duct, 40 va transformer minimum, Cr1 cr2 gv1 gv2

Advertising
background image

Component & System Wiring

84

MODGAS II Controller Wiring When Used With The VCM Controller

FILENAME

DATE:

B. Crews

DESCRIPTION:

PAGE

DRAWN BY:

When Used With Orion VCM Controller

JOB NAME

03/09/06

O-MODGASII-VCM-Wr1.CDR

AAON MODGAS II Wiring

1

Line

GND

24VAC

Mount In

Unit Supply

Air Duct

Supply

Air Temp.

Sensor

Induced

Air Blower

Speed

Control

Hi Speed

Low Speed

Heat Enable

Signal (24 VAC)

W1

CR2-1

SC

CR1-A

CR1-B

L1

L2

N.O.

N.O.

N.O.

N.O.

N.O.

N.C.

40 VA

Transformer

Minimum

Motor

1.)24 VAC Must Be Connected So

That All Ground Wires Remain
Common.

2.)All Wiring To Be In Accordance

With Local And National Electrical
Codes And Specifications.

PHILIPS

EPROM

U3

U5

RAM

CX2

1

U2

R1

C3

U4

CX3

CX4

YS101818

552

PROCESSOR

BOARD

CX5

C1

U1

R2

CX1

CX6

WDOG

U6

PHILIPS

P1

C2

C4

V1

V3

K3

V2

K2

FT

K1

TB1

DISCHARGE

SETPOINT

F

F

1

1

O

O

F

F

RESET

LIMIT

AUX

COM

AUX

LO SPD

FAN

LO

SPD

FA

N

ADD

ADD

4

4

2

2

16

16

8

8

64

64

32

32

128

128

R4

GAS

VA

LV

E

SER.

#:

VOUT

D9

V5

C13

GND

TB4

POWER

YS101826PREV

1

MODULA

TING

GAS

BOARD

PJ1

SHLD

RV

1

STATUS

P1

R8

RST IN

J01

AUX IN

GND

HEAT EN

C2

R1

R3

R1

P

D2

R9

C1

SAT

+VDC

VR1

R7

D1

R15

P

I2C IN

TB2

R

T

V4

GND

24V

AC

D8

U5

C7

R25

R26

R26

C6

POWER

TB3

CR1

CR2

GV1

GV2

2 Gas
Valves Can
Be Connected
As Shown

Modular Cable Connects To

HVAC Unit Controller

Caution:

If your HVAC unit is supplied with the MODGAS II controller with or without an MHGRV II controller, the Supply Air Temperature Sensor must always

be wired to the MODGAS II controller. If your HVAC unit is supplied with only the MHGRV II controller, the Supply Air Temperature Sensor must be

connected to the MHGRV II controller. If you have either of these controllers on your HVAC unit and have a Supply Air Temperature Sensor connected

to the VCM controller, your controls will not function correctly. Only one Supply Air Temperature Sensor can be used on an HVAC unit.

Wiring For MODGAS II When Used With Orion VCM Controller

Note:
1.) When The MODGAS II Controller Is Used With The VCM
Controller It Must Have (1) Relay Output On The VCM Controller
Configured For The MODGAS II Controller In Order To Function
Correctly. This Relay Output Must Be Configured When Setting-up
The Controller(s) Operating Parameters. See the VCM Controller
Operator Interfaces Technical Guide For Complete Controller
Programming and Configuration Information.