8 technical data, 1 sunny central 200, Technical data – SMA SC 200 Installation User Manual

Page 81: Sunny central 200

Advertising
background image

SMA Solar Technology AG

Technical Data

Installation Guide

SC20_25_35-IEN094521

81

8 Technical Data

8.1 Sunny Central 200

Input Specifications

Output Values

Efficiency

Dimensions

Nominal power DC

P

PV

210 kW

Maximum PV power (recommended)

P

PV

230 kWp

a)

a)

Specifications apply for irradiation values = 1,000 (kWh / kWp x year)

DC voltage range (MPPT)

U

DC

450 V – 820 V

b)

b)

U

DCmin

at U

AC,Nom

+/– 5 % and cos ϕ = 1

Maximum permissible DC voltage

U

DC

880 V

Maximum permissible DC voltage with EVR

U

DC EVR

1000 V (optional)

Maximum permissible DC current

I

DC

472 A

Voltage ripple, PV voltage

U

PP

< 3 %

Number of DC inputs / connection points

5 / DC fuses

Nominal AC output power

P

AC

200 kW

a)

a)

P

nom

at U

AC,Nom

+ 5 % and cos ϕ = 1

Operating grid voltage +/– 10 %

U

AC

400 V

Nominal AC current

I

AC,Nom

289 A

Grid structure

TT, TN-S, TN-C

Operating range, grid frequency

f

AC

50 Hz - 60 Hz

Harmonic distortion of grid current

< 3 % at nominal power

Power factor

cos ϕ

> 0.98 % at nominal power

Max. efficiency P

AC, max

η

95.7 %

Euro-Eta

η

euro

94.5 %

Width / Height / Depth (W / H / D)

a)

(Standard)

a)

The switch cabinet is raised by 210 mm for the EVR option.

800 mm + 1200 mm / 2120 mm / 850 mm

Width / Height / Depth (W / H / D)

b)

(for "Protection against chemically active
substances" option)

b)

The switch cabinet is raised by 210 mm for the EVR option.

1200 mm + 1200 mm / 2120 mm / 850 mm

Weight: approx.

1600 kg