Installation Orientation and Spacing

Install the drive upright as illustrated in

Figure i.5

to maintain proper cooling.

Figure i.5 Correct Installation Orientation

NOTICE:

Install the drive upright as specified in the manual. Failure to comply may damage the drive due to improper cooling.

n

Single Drive Installation

Figure i.6

shows the installation distance required to maintain sufficient space for airflow and wiring. Install the heatsink

against a closed surface to avoid diverting cooling air around the heatsink.

A

A

B

B

Side Clearance

Top/Bottom Clearance

C

C

D

D

A – 50 mm minimum

B – 30 mm minimum

C – 120 mm minimum

D – Airflow direction

Figure i.6 Correct Installation Spacing

Note:

IP20/NEMA Type 1 enclosure and IP00/Open Type enclosure models require the same amount of space above and below the drive for

installation.

n

Multiple Drive Installation (Side-by-Side Installation)

Models 2A0004 to 2A0081, 4A0002 to 4A0044, and 5A0003 to 5A0032 can take advantage of Side-by-Side installation.
When installing multiple drives into the same enclosure panel, mount the drives according to

Figure i.6

and set L8-35,

Installation Method Selection, to 1 (Side-by-Side Mounting).
When mounting drives with the minimum clearance of 2 mm according to

Figure i.7

, set parameter L8-35 to 1 while

considering derating.

i.2 Mechanical Installation Safety

YASKAWA ELECTRIC TOEP YAIP1U 03B YASKAWA AC Drive – P1000 Safety Precautions