I.3 electrical installation safety – Yaskawa CIMR-PU User Manual

Page 34

Advertising
background image

Drive Model

Wire Gauge (AWG, kcmil)

Screw

Size

Crimp

Terminal

Model Number

Tool

Insulation Cap

Model No.

Code

<1>

R/L1, S/L2, T/L3 U/T1, V/T2, W/T3

Machine No.

Die Jaw

4A0362

3/0 × 2P

M12

80-L12

YF-1

YET-300-1

TD-323,

TD-312

TP-080

100-051-558

4/0 × 2P

100-L12

TD-324,

TD-312

TP-100

100-051-560

250 × 2P

150-L12

TD-325,

TD-313

TP-150

100-051-562

300 × 2P
350 × 2P

180-L12

TD-327,

TD-314

TP-200

100-066-688

400 × 2P

200-L12

100-051-564

500

325-12

TD-328,

TD-315

TP-325

100-051-277

600

4A0414

4/0 × 2P

M12

100-L12

YF-1

YET-300-1

TD-324,

TD-312

TP-100

100-051-560

250 × 2P

150-L12

TD-325,

TD-313

TP-150

100-051-562

300 × 2P

4A0515

3/0 × 4P

3/0 × 4P

M12

80-L12

YF-1

YET-300-1

TD-323,

TD-312

TP-080

100-051-558

4/0 × 4P

4/0 × 4P

100-L12

TD-324,

TD-312

TP-100

100-051-560

250 × 4P

150-L12

TD-325,

TD-313

TP-150

100-051-562

300 × 2P

4A0675

4/0 × 4P

M12

100-L12

YF-1

YET-300-1

TD-324,

TD-312

TP-100

100-051-560

250 × 4P

150-L12

TD-325,

TD-313

TP-150

100-051-562

300 × 4P

4A0930

3/0 × 8P

M12

80-L12

YF-1

YET-300-1

TD-323,

TD-312

TP-080

100-051-558

4/0 × 8P

100-L12

TD-324,

TD-312

TP-100

100-051-560

250 × 8P

150-L12

TD-325,

TD-313

TP-150

100-051-562

300 × 8P

4A1200

4/0 × 8P

M12

100-L12

YF-1

YET-300-1

TD-324,

TD-312

TP-100

100-051-560

250 × 8P

150-L12

TD-325,

TD-313

TP-150

100-051-562

300 × 8P

<1> Codes refer to a set of three crimp terminals and three insulation caps. Prepare input and output wiring using two sets for each connection.

Example 1: Models with 300 kcmil for both input and output require one set for input terminals and one set for output terminals, so the user should
order two sets of [100-051-272].
Example 2: Models with 4/0 AWG × 2P for both input and output require two sets for input terminals and two sets for output terminals, so the user
should order four sets of [100-051-560].

Note:

Use crimp insulated terminals or insulated shrink tubing for wiring connections. Wires should have a continuous maximum allowable

temperature of 75 °C 600 Vac UL-approved vinyl-sheathed insulation.

i.3 Electrical Installation Safety