Start up, Drive setup procedure, Power on – Yaskawa CIMR-PU User Manual

Page 47: I.5 start up

Advertising
background image

i.5

Start Up

u

Drive Setup Procedure

Figure i.24

summarizes steps to start the drive and gives quick references to familiarize the user with start-up procedures.

YES

NO

START

Install and wire the drive as explained in Chapters 1, 2, and 3.

Apply main power to the drive while following safety guidelines.

Application Presets

A1-03 used?

Refer to
Application
Selection Section

Set the basic parameters

b1-01/b1-02 for frequency reference selection and run command source selection

H1-oo,H2-oo,H3-oo,H4-oo,H6-oo for I/O terminal setting

d1-oo for using multi-speed references

C1-oo and C2-oo for accel/decel and S-curve time settings

L8-55 = 0 if using a regen converter

L3-04 if using dynamic braking options

NO

YES

YES

NO

Run the motor without load; check the rotation direction and operation.

Verify external signal commands to the drive work as desired.

Couple the load or machine to the motor.

Run the machine and check for desired operation.

Fine tune parameters. Adjust application settings if necessary.

Check the machine operation and verify parameter settings.

Drive is ready to run the application.

Energy Savings (b8-01 = 1)

or Speed Estimation Search (b3-24 = 1)

enabled when b3-01 = 1 or L2-01 = 1, 2?

Is the motor cable

longer than 50 meters?

Set or verify the V/f pattern settings E1-oo.

Perform Rotational Auto-Tuning

for V/f Control (T1-01 = 3)

Perform Stationary Auto-Tuning

for Stator Resistance (T1-01 = 2)

Figure i.24 Simple Setup with Energy Savings or Speed Search

Note:

1. Execute Stationary Auto-Tuning for Line-to-Line Resistance if the drive has been Auto-Tuned and then moved to a different location

where the motor cable length exceeds 50 m.

2. Perform Auto-Tuning again after installing an AC reactor or other such components to the output side of the drive.

u

Power On

Before turning on the power supply:
• Make sure all wires are connected properly.
• Make sure no screws, loose wire ends or tools are left in the drive.
• After turning the power on, the drive mode display should appear and no fault or alarm should be displayed.

i.5 Start Up

YASKAWA ELECTRIC TOEP YAIP1U 03B YASKAWA AC Drive – P1000 Safety Precautions

47

Advertising
This manual is related to the following products: