Operator programing errors – Yaskawa CIMR-PU User Manual

Page 58

Advertising
background image

u

Operator Programing Errors

An Operator Programming Error (oPE) occurs when an inapplicable parameter is set or an individual parameter setting is

inappropriate. When an oPE error is displayed, press the ENTER button to display U1-18 (oPE fault constant) and show the

parameter causing the oPE error.

Digital

Operator

Cause

Possible Solution

oPE01

The drive model selection (o2-04) and the actual capacity of the

drive are not the same.

Correct the value set to o2-04.

oPE02

Parameters were set outside the possible setting range.

Use U1-18 to find parameters set outside the range. and set

parameters to the proper values.

oPE03

A contradictory setting is assigned to multi-function contact inputs

H1-01 to H1-08 (Excludes “Not used” and “External Fault.”)

Ensure all multi-function inputs are assigned to different functions.

The Up command was set but the Down command was not, or vice

versa (settings 10 vs. 11).

Properly set the functions that required for use in combination with

other functions.

The Up 2 command was set but the Down 2 command was not, or

vice versa (settings 75 vs. 76).
• Run/Stop command for a 2-wire sequence was set (H1-oo =

42), but Forward/Reverse command (H1-oo = 43) was not.

• “Drive Enable” is set to multi-function input S1 or S2 (H1-01 =

6A or H1-02 = 6A).

Properly set the functions that required for use in combination with

other functions.

oPE04

The drive, control board, or terminal board have been replaced and

the parameter settings between the control board and the terminal

board no longer match.

Set A1-03 to 5550 to load the parameter settings stored in the

terminal board to the drive. Initialize parameters after drive

replacement by setting A1-03 to 1110 or 2220.

oPE05

Frequency reference is assigned to an option card (b1-01 = 3) and

an input option card is not connected to the drive.

Reconnect the input option card to the drive.

The Run command is assigned to an option card (b1-02 = 3) and an

input option card is not connected to the drive.
Frequency reference is assigned to the pulse train input (b1-01 = 4)

and terminal RP is not set for frequency reference input (H6-01 >

0)

Set H6-01 to 0.

oPE07

At least two analog input terminals are set to the same function (i.e.,

at least two of these parameters have the same setting: H3-02,

H3-10, or H3-06).

Change the settings to H3-02, H3-10, and H3-06 so that functions

no longer conflict.

Note: Both 0 (Frequency Reference Bias) and F (Not Used) can be

set to H3-02, H3-10, or H3-06 simultaneously.

The following simultaneous contradictory settings:
• H3-02, H3-10, or H3-06 = B (PID Feedback) while H6-01

(Pulse Train Input) = 1 (PID Feedback)

• H3-02, H3-10, or H3-06 = C (PID Target Value) while H6-01 =

2

(pulse train input sets the PID target value)

• H3-02, H3-10, or H3-06 = C (PID Target Value) while b5-18 =

1

(enables b5-19 as the target PID value)

• H6-01 = 2 (PID target) while b5-18 = 1

(enables b5-19 as the target PID value)

Disable one of the PID selections.

oPE09

The following simultaneous contradictory settings have occurred:
• b5-15 is not set to 0.0 (PID Sleep Function Operation Level)
• The stopping method is set to either DC Injection Braking or coast

to stop with a timer (b1-03 = 2 or 3).

• Set b5-15 to a value other than 0.0.
• Set the stopping method to coast to stop or ramp to stop (b1-03

= 0 or 1).

oPE10

V/f pattern setting error.

E1-09 ≤ E1-07 < E1-06 ≤ E1-11 ≤ E1-04

Correct the settings for E1-04, E1-06, E1-07, E1-09, and E1-11.

oPE11

The following simultaneous contradictory settings have occurred:

C6-05 > 6 and C6-04 > C6-03 (carrier frequency lower limit is

greater than the upper limit).

If C6-05 ≤ 6, the drive operates at C6-03.

Correct the parameter settings.

The upper and lower limits between C6-02 and C6-05 are

contradictory.

oPE28

• S2-01 > S2-02
• S2-06 > S2-07
• S2-11 > S2-12
• S2-16 > S2-17

Correct the parameter settings.

i.7 Troubleshooting

58