I.3 electrical installation safety – Yaskawa CIMR-PU User Manual

Page 30

Advertising
background image

Drive Model

Terminal

Recomm. Gauge

AWG, kcmil

Wire Range

AWG, kcmil

Screw

Size

Tightening Torque

N·m (lb.in.)

5A0062

R/L1, S/L2, T/L3

4

10 to 4/0

M10

18 to 23

(159 to 204)

U/T1, V/T2, W/T3

4

10 to 4/0

⊖, ⊕1

4 to 4/0

⊕3

6 to 4/0

4

4

5A0077

R/L1, S/L2, T/L3

3

10 to 4/0

M10

18 to 23

(159 to 204)

U/T1, V/T2, W/T3

3

10 to 4/0

⊖, ⊕1

3 to 4/0

⊕3

6 to 4/0

4

4

5A0099

R/L1, S/L2, T/L3

1/0

10 to 4/0

M10

18 to 23

(159 to 204)

U/T1, V/T2, W/T3

1

10 to 4/0

⊖, ⊕1

2 to 4/0

⊕3

4 to 4/0

4

4

5A0125

R/L1, S/L2, T/L3

2/0

1 to 300

M10

18 to 23

(159 to 204)

U/T1, V/T2, W/T3

2/0

1 to 300

⊖, ⊕1

2/0 to 3/0

⊕3

1 to 1/0

3

4 to 300

5A0145

R/L1, S/L2, T/L3

3/0

2/0 to 300

M10

18 to 23

(159 to 204)

U/T1, V/T2, W/T3

3/0

2/0 to 300

⊖, ⊕1

3/0 to 4/0

⊕3

1/0 to 2/0

3

4 to 300

5A0192

R/L1, S/L2, T/L3

300

2/0 to 600

M12

32 to 40

(283 to 354)

U/T1, V/T2, W/T3

250

2/0 to 600

⊖, ⊕1

2/0 to 400

⊕3

2/0 to 250

M10

18 to 23

(159 to 204)

1

1 to 350

M12

32 to 40

(283 to 354)

5A0242

R/L1, S/L2, T/L3

400

2/0 to 600

M12

32 to 40

(283 to 354)

U/T1, V/T2, W/T3

350

2/0 to 600

⊖, ⊕1

2/0 to 500

⊕3

250 to 300

M10

18 to 23

(159 to 204)

1

1 to 350

M12

32 to 40

(283 to 354)

Note:

When connecting peripheral devices or options to terminals

⊖, ⊕1, ⊕3, B1, and B2 , refer to the instruction manual for each device. For

more information, contact Yaskawa or your nearest sales representative.

i.3 Electrical Installation Safety

30

YASKAWA ELECTRIC TOEP YAIP1U 03B YASKAWA AC Drive – P1000 Safety Precautions

Advertising