Altitude derating, Dimensions, weight, heat loss, Dimensions, weight, heat loss notice – Yaskawa CIMR-PU User Manual

Page 68

Advertising
background image

Setting 2: IP20/NEMA Type 1 Enclosure

Drive operation between -10 °C and +40 °C allows 100% continuous current without derating. Operation between +40 °C and

+50 °C requires output current derating.

Setting 3: External Heatsink Installation, Finless Drive

Drive operation between -10 °C and +40 °C allows 100% continuous current without derating. Operation between +40 °C and

+50 °C requires output current derating.

100

85

70

55

0

L8-35 = 2: IP20/NEMA Type 1 Enclosure
L8-35 = 3: External Heatsink lnstallation

L8-35 = 0: IP00/Open-Chassis Enclosure

30

-10

40

50

Drive Rating

(%)

L8-12
(Ambient temp:

°C)

L8-35 = 1: Side-by-Side Mounting

Figure i.29 Ambient Temperature and Installation Method Derating

u

Altitude Derating

The drive standard ratings are valid for installation altitudes up to 1000 m. For installations from 1000 m to 3000 m, the drive

rated voltage and the rated output current must be derated for 0.2% per 100 m.

u

Dimensions, Weight, Heat Loss

NOTICE

Refer to the Mechanical Installation Chapter and the Specifications Chapter of the P1000 Technical Manual
SIEPYAIP1U01
which can be found on the CD-ROM packaged with the product.

i.9 European Standards

68

YASKAWA ELECTRIC TOEP YAIP1U 03B YASKAWA AC Drive – P1000 Safety Precautions