<2> Set L8-55 to 0 to disable the protection function of the built-in braking transistor of the drive when using an optional regenerative

converter or dynamic braking option. Leaving L8-55 enabled may cause a braking resistor fault (rF). Additionally, disable Stall

Prevention (L3-04 = 0) when using an optional regenerative converter, regenerative or braking units, or dynamic braking option.

Leaving If L3-04 enabled may prevent the drive from stopping within the specified deceleration time.

<3> Supplying power to the control circuit separately from the main circuit requires 24 V power supply (option).
<4> This figure illustrates an example of a sequence input to S1 through S8 using a non-powered relay or an NPN transistor. Install

the wire link between terminals SC-SP for Sink mode, between SC-SN for Source mode, or leave the link out for external power

supply. Never short terminals SP and SN, as it will damage the drive.

<5> This voltage source supplies a maximum current of 150 mA.
<6> The maximum output current capacity for the +V terminal on the control circuit is 20 mA. Never short terminals +V and AC, as

it can cause erroneous operation or damage the drive.

<7> Set jumper S1 to select between a voltage or current input signal to terminal A2. The default setting is for current input.
<8> Set jumper S1 to select between a voltage or current input signal to terminal A1 and A3. The default setting is for voltage input.
<9> Set DIP switch S2 to the ON position to enable the termination resistor in the last drive in a MEMOBUS/Modbus network.
<10> Monitor outputs work with devices such as analog frequency meters, ammeters, voltmeters, and wattmeters. They are not

intended for use as a feedback-type signal.

<11> Use jumper S5 to select between voltage or current output signals at terminals AM and FM. Set parameters H4-07 and H4-08

accordingly.

<12> Self-cooling motors do not require the same wiring necessary for motors with cooling fans.