Name

Description

H5-11

Communications

ENTER Function

Selection

0: Drive requires an Enter command before

accepting any changes to parameter

settings.

1: Parameter changes are activated

immediately without the Enter

command.

H5-12

Run Command

Method Selection

0: FWD/Stop, REV/Stop

1: Run/Stop, FWD/REV

H6-01

Pulse Train Input

Terminal RP Function

Selection

0: Frequency reference

1: PID feedback value

2: PID setpoint value

H6-02

Pulse Train Input

Scaling

Sets the terminal RP input signal frequency

that is equal to 100% of the value selected

in H6-01.

H6-03

Pulse Train Input Gain

Sets the level of the value selected in H6-01

when a frequency with the value set in

H6-02 is input.

H6-04

Pulse Train Input Bias Sets the level of the value selected in H6-01

when 0 Hz is input.

H6-05

Pulse Train Input Filter

Time

Sets the pulse train input filter time

constant.

H6-08

Pulse Train Input

Minimum Frequency

Sets the minimum frequency for the pulse

train input to be detected. Enabled when

H6-01 = 0, 1, or 2.

L2-01

Momentary Power

Loss Operation

Selection

0: Disabled. Drive trips on Uv1 fault when

power is lost.

1: Recover within the time set in L2-02. Uv1

will be detected if power loss is longer than

L2-02.

2: Recover as long as CPU has power.

Uv1 is not detected.

3: KEB deceleration for the time set to

L2-02.

4: KEB deceleration as long as CPU has

power.

5: KEB deceleration to stop.

L3-04

Stall Prevention

Selection during

Deceleration

0: Disabled. Deceleration at the active

deceleration rate. An ov fault may occur.

1: General purpose. Deceleration is

paused when the DC bus voltage exceeds

the Stall Prevention level.

2: Intelligent. Decelerate as fast as possible

while avoiding ov faults.

3: Stall Prevention with braking resistor.

Stall Prevention during deceleration is

enabled in coordination with dynamic

braking.

4: Overexcitation Deceleration.

Decelerates while increasing the motor

flux.

5: Overexcitation Deceleration 2. Adjust

the deceleration rate according to the DC

bus voltage.

L5-01

Number of Auto

Restart Attempts

Sets the number of times the drive may

attempt to restart after the following faults

occur: GF, LF, oC, ov, PF, rH, rr, oL1, oL2,

oL3, oL4, STo, Uv1.

No.

Name

Description

L6-01

Torque Detection

Selection 1

0: Disabled

1: oL3 detection only active during speed

agree, operation continues after detection

2: oL3 detection always active during run,

operation continues after detection

3: oL3 detection only active during speed

agree, output shuts down on an oL3 fault

4: oL3 detection always active during run,

output shuts down on an oL3 fault

5: UL3 detection only active during speed

agree, operation continues after detection

6: UL3 detection always active during run,

operation continues after detection

7: UL3 detection only active during speed

agree, output shuts down on an oL3 fault

8: UL3 detection always active during run,

output shuts down on an oL3 fault

9: UL6 Alarm at Speed Agree

10: UL6 Alarm during Run

11: UL6 Fault at Speed Agree

12: UL6 Fault during Run

L6-02

Torque Detection

Level 1

Sets the overtorque and undertorque

detection level.

L6-03

Torque Detection Time

1

Sets the time an overtorque or undertorque

condition must exist to trigger torque

detection 1.

L8-55

Internal Braking

Transistor Protection

0: Disabled. Disable when using a regen

converter or optional braking unit.

1: Protection enabled.

o1-03

Digital Operator

Display Selection

0: 0.01 Hz

1: 0.01% (100% = E1-04)

2: r/min (calculated using the number of

motor poles setting in E2-04)

3: User-selected units (set by o1-09, o1-10

and o1-11)

o1-06

User Monitor Selection

Mode

0: 3 Monitor Sequential (displays the

next two sequential monitors)

1: 3 Monitor Selectable (set by o1-07 and

o1-08)

o1-07

Second Line Monitor

Selection

Selects the monitor that is shown in the

second line.

Enter the last three digits of the monitor

parameter number to be displayed:

Uo-oo. For example, set "403" to display

monitor parameter U4-03.

o1-08

Third Line Monitor

Selection

Selects the monitor that is shown in the third

line.

Enter the last three digits of the monitor

parameter number to be displayed:

Uo-oo. For example, set "403" to display

monitor parameter U4-03.

T1-01

Auto-Tuning Mode

Selection

2: Stationary Auto-Tuning for Line-to-

Line Resistance

3: Rotational Auto-Tuning for V/f Control

(necessary for Energy Savings and Speed

Estimation Speed Search)

i.6 Parameter Table