NOTICE

Check all the wiring to ensure that all connections are correct after installing the drive and connecting any other
devices.
Failure to comply could result in damage to the drive.
Do not connect power supply lines to output terminals U/T1, V/T2, or W/T3. Failure to comply will destroy the drive.
Be sure to perform a final check of all sequence wiring and other connections before turning on the power and also check
for short circuits on the control terminals, which may damage the drive.
To get the full performance life out of the electrolytic capacitors and circuit relays, refrain from switching the drive
power supply off and on more than once every 30 minutes.
Frequent use can damage the drive. Use the drive to stop and
start the motor.

NOTICE

Install a fuse and a GFCI in models 4A0930 and 4A1200. Failure to comply may result in serious damage to the facilities
if the drive is defective.

Refer to Wiring Fuses for Models 4A0930 and 4A1200 on page 22

for details.

i.3 Electrical Installation Safety

YASKAWA ELECTRIC TOEP YAIP1U 03B YASKAWA AC Drive – P1000 Safety Precautions

17