CSA for Industrial Control Equipment

The drive is CSA-certified as Industrial Control Equipment Class 3211.
Specifically, the drive is certified to: CAN/CSA C22.2 No. 04-04 and CAN/CSA C22.2 No.14-05.

u

Drive Motor Overload Protection

Set parameter E2-01 (motor rated current) to the appropriate value to enable motor overload protection. The internal motor

overload protection is UL listed and in accordance with the NEC and CEC.

n

E2-01: Motor Rated Current

Setting Range: Model-dependent
Default Setting: Model-dependent
Parameter E2-01 protects the motor when parameter L1-01 is not set to 0. The default for L1-01 is 1, which enables protection

for standard induction motors.
If Auto-Tuning has been performed successfully, the motor data entered to T1-04 is automatically written to parameter E2-01.

If Auto-Tuning has not been performed, manually enter the correct motor rated current to parameter E2-01.

n

L1-01: Motor Overload Protection Selection

The drive has an electronic overload protection function (oL1) based on time, output current, and output frequency that protects

the motor from overheating. The electronic thermal overload function is UL-recognized, so it does not require an external

thermal relay for single motor operation.
This parameter selects the motor overload curve used according to the type of motor applied.

Table i.23 Overload Protection Settings

Setting

Description

0

Disabled

Disabled the internal motor overload protection of the drive.

1

Standard fan-cooled motor (60 Hz default)

Selects protection characteristics for a standard self-cooled motor with limited cooling capabilities

when running below the rated speed. The motor overload detection level (oL1) is automatically

reduced when running below the motor rated speed.

2

Drive duty motor with a speed range of 1:10

Selects protection characteristics for a motor with self-cooling capability within a speed range of

10:1. The motor overload detection level (oL1) is automatically reduced when running below

1/10 of the motor rated speed.

3

Vector motor with a speed range of 1:100

Selects protection characteristics for a motor capable of cooling itself at any speed including zero

speed (externally cooled motor). The motor overload detection level (oL1) is constant over the

entire speed range.

6

Standard fan-cooled motor (50 Hz)

Selects protection characteristics for a standard self-cooled motor with limited cooling capabilities

when running below the rated speed. The motor overload detection level (oL1) is automatically

reduced when running below the motor rated speed.

When connecting the drive to more than one motor for simultaneous operation, disable the electronic overload protection

(L1-01 = 0) and wire each motor with its own motor thermal overload relay.
Enable motor overload protection (L1-01

≠ 0) when connecting the drive to a single motor, unless another motor overload

preventing device is installed. The drive electronic thermal overload function causes an oL1 fault, which shuts off the output

of the drive and prevents additional overheating of the motor. The motor temperature is continually calculated while the drive

is powered up.