Terminal configuration, Control circuit input terminals, I.3 electrical installation safety – Yaskawa CIMR-PU User Manual

Page 36

Advertising
background image

u

Terminal Configuration

The control circuit terminals are arranged as shown in

Figure i.12

.

E(G) IG R+ R- S+ S-

S1 S2 S3 S4 S5 S6 S7 S8 SN SC SP

V+ AC A1 A2 A3 FM AM AC

24V

RP AC

M1 M2 M3 M4

MD ME MF

MA MB MC

E(G) IG R+ R- S+ S-

S1 S2 S3 S4 S5 S6 S7 S8 SN SC SP

V+ AC A1 A2 A3 FM AM AC

24V

RP AC

M1 M2 M3 M4

MD ME MF

MA MB MC

Figure i.12 Control Circuit Terminal Arrangement

u

Control Circuit Input Terminals

Table i.9

lists the input terminals on the drive. Text in parenthesis indicates the default setting for each multi-function input.

Table i.9 Control Circuit Input Terminals

Type

No.

Terminal Name (Function)

Function (Signal Level) Default Setting

Multi-Function

Digital Inputs

S1

Multi-function input 1

(Closed: Forward run, Open: Stop)

• Photocoupler
• 24 Vdc, 8 mA

Refer to Sinking/Sourcing Mode for Digital Inputs on page 41

.

S2

Multi-function input 2

(Closed: Reverse run, Open: Stop)

S3

Multi-function input 3

(External fault, N.O.)

S4

Multi-function input 4

(Fault reset)

S5

Multi-function input 5

(Multi-step speed reference 1)

S6

Multi-function input 6

(Multi-step speed reference 2)

S7

Multi-function input 7

(Jog reference)

S8

Multi-function input 8

(Baseblock command (N.O.))

SC

Multi-function input common

Multi-function input common

SP

Digital input power supply +24 Vdc

24 Vdc power supply for digital inputs, 150 mA max

NOTICE:

Do not jumper or short terminals SP and SN. Failure to

comply will damage the drive.

SN

Digital input power supply 0 V

24 V transducer power supply 0 V

i.3 Electrical Installation Safety