Fault reset methods, I.7 troubleshooting – Yaskawa CIMR-PU User Manual

Page 60

Advertising
background image

Digital

Operator

Cause

Possible Solution

Er-12

Current Detection Error

One of the motor phases is missing: (U/T1, V/T2, W/T3).

Check motor wiring and correct any problems.

The current exceeded the current rating of the drive.

• Check motor wiring for a short between motor lines.
• Close any magnetic contactors used between motors.
• Replace the control board or the entire drive. For instructions on

replacing the control board, contact Yaskawa or your nearest

sales representative.

The current is too low.

Er-13

Leakage Inductance Error

Drive was unable to complete tuning for leakage inductance within

300 seconds.

• Check all wiring and correct any mistakes.
• Check the motor rated current value written on the motor

nameplate and enter the correct value to T1-04.

Er-17

Reverse Prohibited Error

Drive is prohibited from rotating the motor in reverse while

attempting to perform Inertia Tuning.

• Inertia Auto-Tuning cannot be performed if the drive is restricted

from rotating in reverse.

• Assuming it is acceptable for the application to rotate in reverse,

set b1-04 to 0 and then perform Inertia Tuning.

u

Fault Reset Methods

When a fault occurs, the cause of the fault must be removed and the drive must be restarted. The table below lists the different

ways to restart the drive.

After the Fault Occurs

Procedure

Fix the cause of the fault, restart the drive, and

reset the fault

Press

on the digital operator when the error code

is displayed.

LO

RE

F2

F1

ESC

RUN

STOP

ENTER

RESET

RESET

- MODE -

oC

Overcurrent

DRV

FWD

RESET

Resetting via Fault Reset Digital Input S4

Close then open the fault signal digital input via

terminal S4. S4 is set for “Fault Reset” as default

(H1-04 = 14).

Fault Reset Switch

Drive

S4 Fault Reset Digital Input

SC Digital Input Common

Turn off the main power supply if the above methods do not reset the fault. Reapply power after the

digital operator display has turned off.

ON

OFF

2

1

Note:

If the Run command is present, the drive will disregard any attempts to reset the fault. Remove the Run command before attempting to clear

a fault situation.