Explained in, Table i.14, Table i.15 – Yaskawa CIMR-PU User Manual

Page 42

Advertising
background image

V

I

A1 A2 A3

Jumper S1

Figure i.19 Terminal A2 Set to Current Input; A1 and A3 Set to Voltage Input

Table i.14 Jumper S1 Settings

Setting

Description

V (top position)

Voltage input (-10 to +10 V or 0 to 10 V)

I (bottom position)

Current input (4 to 20 mA or 0 to 20 mA)

Table i.15 Voltage/Current Selection Parameter Details

No.

Parameter Name

Description

Setting

Range

Default

Setting

H3-01

Terminal A1 signal level selection

Selects the signal level for terminal A1.

0: 0 to 10 Vdc

1: 0 to 10 Vdc Bipolar

2: 4 to 20 mA

3: 0 to 20 mA

0 to 3

0

H3-05

Terminal A3 signal level selection

Selects the signal level for terminal A3.

0: 0 to 10 Vdc

1: 0 to 10 Vdc Bipolar

2: 4 to 20 mA

3: 0 to 20 mA

0 to 3

0

H3-09

Terminal A2 signal level selection

Selects the signal level for terminal A2.

0: 0 to 10 Vdc

1: 0 to 10 Vdc Bipolar

2: 4 to 20 mA

3: 0 to 20 mA

0 to 3

2

n

Motor Protection Using a Positive Temperature Coefficient (PTC) Thermistor

Connect a motor PTC can to an analog input of the drive for motor overheat protection.
The motor overheat alarm level triggers an oH3 alarm and the drive continues the operation selected in L1-03. The overheat

fault level triggers an oH4 fault, outputs a fault signal, and the drive stops the motor using the stop method selected in L1-04.
Connect the PTC between terminals AC and A3 and install a 12 kOhm resistor between terminals V+ and A3 as shown in

Figure i.20

. Set H3-05 to 0 and H3-06 to E.

Note:

A 12 kOhm resistor must be connected between one of the terminals A1, A2, or A3 and V+ for PTC functionality. Connect the 12 kOhm

resistor to the same terminal as the PTC input. Do not connect terminals V+ to AC, or damage to the drive may result.

P1000 Drive

Multi-function input

PTC
thermistor

A3 (0-10 V)

AC

V+ Power supply
+10.5 Vdc,
max. 20 mA

12 kOhm
resistor

PTC external circuit
(customer supplied)

Figure i.20 Connection of a Motor PTC

i.3 Electrical Installation Safety

42

YASKAWA ELECTRIC TOEP YAIP1U 03B YASKAWA AC Drive – P1000 Safety Precautions