External Reference Selection and Acceleration/Deceleration Times

n

b1-01: Frequency Reference Selection

Set parameter b1-01 according to the frequency reference used.

b1-01

Reference Source

Frequency Reference Input

0

Digital operator

Set the frequency references in the d1-oo parameters and use digital inputs to switch over between

different reference values.

1

Analog input terminals

Apply the frequency reference signal to terminal A1, A2, or A3.

2

MEMOBUS/Modbus

communications

Serial Communications using the RS422/485 port

3

Option PCB

Communications option card

4

Pulse input (terminal RP)

Set the frequency reference at terminal RP using a pulse train signal.

n

b1-02: Run Command Selection

Set parameter b1-02 according to the Run command used.

b1-02

Reference Source

Run Command Input

0

Digital operator

RUN and STOP keys on the operator

1

Digital input terminals

Multi-Function digital input

2

MEMOBUS/Modbus

communications

Serial Communications using the RS-422/RS-485 port

3

Option PCB

Communications option card

n

Acceleration/ Deceleration Times and S-Curves

There are two sets of acceleration and deceleration times which can be set in the C1-oo parameters. The default activated

accel/decel times are C1-01/C1-02. Adjust these times to the appropriate values required by the application. If necessary, S-

curves can be activated in the C2-oo parameters for softer accel/decel start and end.

u

Reference and Run Source

The drive has a LOCAL and a REMOTE mode.

Status

Description

LOCAL

The Run/Stop command and the frequency reference are entered at the operator keypad.

REMOTE

The Run command source entered in parameter b1-02 and the frequency reference source entered in parameter b1-01 are used.

If the drive is operated in the REMOTE mode, make sure that the correct sources for the frequency reference and run command

are set in parameters b1-01/b1-02 and that the drive is in the REMOTE mode.
The LED in the LO/RE key indicates where the Run command is input from.

LO/RE LED

Description

ON

Run command is issued from operator.

OFF

Run command is issued from a different source than the operator.

u

I/O Setup

The default setting functions can be seen in the connection diagram on page

19

.

n

Multi-Function Digital Inputs (H1-oo)

The function of each digital input can be assigned in the H1-oo parameters.

n

Multi-Function Digital Outputs (H2-oo)

The function of each digital output can be assigned in the H2-oo parameters. The setting value of these parameters consist

of 3 digits, where the middle and right digit set the function and the left digit sets the output characteristics (0: Output as

selected; 1: Inverse output).

i.5 Start Up