Csa standards compliance, Low voltage wiring for control circuit terminals, Drive short circuit rating – Yaskawa CIMR-PU User Manual

Page 63

Advertising
background image

Drive Model

Nominal

Output Power

HP

AC Drive Input

Amps

MCCB Rating

Amps

<1>

Time Delay Fuse

Rating Amps

<2>

Non-time Delay

Fuse Rating Amps

<3>

Bussman Semi-

conductor Fuse

Rating (Fuse

Ampere)

<4>

5A0017

15

23

40

40

60

FWP-100B (100)

5A0022

20

31

60

50

90

FWP-100B (100)

5A0027

25

38

75

60

110

FWP-125A (125)

5A0032

30

45

75

75

125

FWP-125A (125)

5A0041

40

44

75

75

125

FWP-175A (175)

5A0052

50

54

100

90

150

FWP-175A (175)

5A0062

60

66

125

110

175

FWP-250A (250)

5A0077

75

80

150

125

225

FWP-250A (250)

5A0099

100

108

175

175

300

FWP-250A (250)

5A0125

125

129

225

225

350

FWP-350A (350)

5A0145

150

158

300

275

450

FWP-350A (350)

5A0192

200

228

400

350

600

FWP-600A (600)

5A0242

250

263

500

450

700

FWP-600A (600)

<1> Maximum MCCB Rating is 15 A, or 200 % of drive input current rating, whichever is larger. MCCB voltage rating must be 600 VAC or greater.
<2> Maximum Time Delay fuse is 175% of drive input current rating. This covers any Class CC, J or T class fuse.
<3> Maximum Non-time Delay fuse is 300% of drive input current rating. This covers any CC, J or T class fuse.
<4> When using semiconductor fuses, Bussman FWH and FWP are required for UL compliance. Select FWH for 200 V Class and 400 V Class models

and FWP fuses for 600 V models.

<5> Class L fuse is also approved for this rating.

n

Low Voltage Wiring for Control Circuit Terminals

Wire low voltage wires with NEC Class 1 circuit conductors. Refer to national state or local codes for wiring. The external

power supply shall be a UL listed Class 2 power supply source or equivalent only.

Table i.22 Control Circuit Terminal Power Supply

Input / Output

Terminal Signal

Power Supply Specifications

Digital inputs

S1 to S8, SC

Use the internal LVLC power supply of the drive. Use class

2 for external power supply.

Analog inputs / outputs

+V, A1, A2, A3, AC, AM, FM

Use the internal LVLC power supply of the drive. Use class

2 for external power supply.

n

Drive Short Circuit Rating

The drive is suitable for use on a circuit capable of delivering not more than 100,000 RMS symmetrical Amperes, 240 Vac

maximum (200 V Class), 480 Vac maximum (400 V Class), and 600 Vac maximum (600 V Class) when protected by Factory

recommended branch circuit protection as specified in this document.

u

CSA Standards Compliance

Figure i.26 CSA Mark

i.8 UL and CSA Standards

YASKAWA ELECTRIC TOEP YAIP1U 03B YASKAWA AC Drive – P1000 Safety Precautions

63

Advertising
This manual is related to the following products: