P1000 drive, I.3 electrical installation safety – Yaskawa CIMR-PU User Manual

Page 19

Advertising
background image

+

-

+

+

+

Terminals -, +1, +2, B1, B2 are

for connection options. Never

connect power supply lines to

these terminals

DC link choke

(option)

U

X

+

-

+

+

+

+

U

X

S

1

S

2

S

3

S

4

S

5

S

6

S

7

RP

A

1

A

2

A

3

0 V

AC

R
R
S
S-

IG

P1000 Drive

B

1

1

2

B

2

2 k

S

8

SC

0 V

FM

AM
AC

E (G)

<1>

<2>

<10>

<7>

<9>

<6>

<4>

<3>

+

24 V

+

V

MD

M

1

M

2

ME
MF

Jumper

Braking resistor

(option)

Forward Run / Stop

Reverse Run / Stop

External fault

Fault reset

Multi-speed step 1

Multi-speed step 2

External Baseblock

Jog speed

Multi-function

digtial inputs

(default setting)

Sink / Source mode

selection wire link

(default: Sink)

CN5-C

CN5-B

CN5-A

Option board

Pulse Train Input (max 32 kHz)

Shield ground terminal

Multi-function

analog/pulse

train inputs

Power supply +10.5 Vdc, max. 20 mA

Analog Input 1 (Frequency Reference Bias)

0 to +/-10Vdc (20 kΩ)

4 to 20 mA (250 Ω) / 0 to 20 mA (250 Ω)


MEMOBUS/Modbus comm.

RS-422/RS-485

max. 115.2 kBps

Termination resistor

(120 , 1/2 W)

DIP

Switch S2

Multi-function relay output (Speed Agree H2-03)

250 Vac, max. 1 A

30 Vdc, max 1 A

(min. 5 Vdc, 10 mA)

Multi-function relay output (During Run H2-01)

250 Vac, max. 1 A

30 Vdc, max 1 A

(min. 5 Vdc, 10 mA)

Multi-function analog output 1
(Output frequency)

-10 to +10 Vdc (2mA)
or 4 to 20 mA

Main Circuit

Control Circuit

shielded line

twisted-pair shielded line

main circuit terminal

control circuit terminal

R/L1
S/L2
T/L3

R
S
T

Main

Switch

Fuse

EMC
Filter

M

3

M

4

Multi-function relay output (Zero Speed H2-02)

250 Vac, max. 1 A

30 Vdc, max 1 A

(min. 5 Vdc, 10 mA)

SP

SN

<8>

AM

FM

V

I

Off

On

DIP Switch S2

Term. Res. On/Off

Jumper S1
A1/A2/A3 Volt./Curr.
Selection

Jumper S5

AM/FM Volt./Curr.

Selection

Terminal board

jumpers and switches

FM

+

AM

<5>

<11>

<10>

Multi-function analog output 2
(Output current)

-10 to +10 Vdc (2mA)
or 4 to 20 mA

Three-Phase
Power Supply
200 to 600 V
50/60 Hz

<12>

M

U/T

1

V/T

2

W/T

U

FU
FV
FW

V

W

3

Ground

Cooling fan

M

connectors

(Depending on
model capacity)

Analog Input 2 (Frequency Reference Bias)

0 to +10Vdc (20 kΩ)

4 to 20 mA (250 Ω) / 0 to 20 mA (250 Ω)

Analog Input 3 (Aux. Frequency Reference)

0 to +/-10Vdc (20 kΩ)

4 to 20 mA (250 Ω) / 0 to 20 mA (250 Ω)

Fault output

250 Vac, max. 1 A

30 Vdc, max 1 A

(min. 5 Vdc, 10 mA)

MA
MB
MC

Note: When A1 & A3 using current input

Resolution = 10 bit plus sign

V

I

A1 A2 A3

24V

SN

+24 Vdc

Transducer

Supply

(max. 150 mA)

+

Models 4A0930 and 4A1200
are compatible with
12-Phase Rectification.

Figure i.9 Drive Standard Connection Diagram (example: model 2A0040)

<1> Remove the jumper when installing a DC link choke. Models 2A0110 to 2A0415 and 4A0058 to 4A1200 come with a built-in

DC link choke.

i.3 Electrical Installation Safety

YASKAWA ELECTRIC TOEP YAIP1U 03B YASKAWA AC Drive – P1000 Safety Precautions

19