Installation and wiring, Verify drive operation – Yaskawa V7 PROFIBUS-DP User Manual

Page 12

Advertising
background image

Installation 1-6

Installation and Wiring

The following describes the installation and configuration of the V7 PROFIBUS-DP Option. For detailed information please refer to the
appropriate sections of this manual or the V7 Technical Manual.

‹ Verify Drive Operation

„ Connect power to the drive and verify that the drive functions properly. This includes running the drive from the operator

keypad. Refer to the V7 Technical Manual, for information on connecting and operating the drive.

„ Remove power from the drive and wait for the charge lamp to be completely extinguished. Wait at least five additional minutes

for the drive to be completely discharged. Measure DC bus voltage and verify that it is at a safe level.

„ Remove the operator keypad and terminal cover.

‹ Remove CN2 Protective Cover and Install Mounting Bracket

Remove the plastic protective cover from the CN2 connector on the drive by cutting the three tabs as shown below. Install the option
mounting bracket and secure it to the drive with the M3x8 screw provided.

Align hole in
mounting bracket
with nib on front of
the V7 drive

Secure mounting
bracket to V7 drive
with M3x8 screw
provided

Remove the CN2
protective cover
by carefully
clipping the
three tabs

Option kit mounting
bracket

C

N

2 C

o

ver

Figure 1.2 – Remove CN2 Cover and Install Option Mounting Bracket

Advertising