Installation 1-13

Drive Faults

The following is a table of faults caused by the communication option that will be displayed on the V7 Operator Keypad, their causes, and
possible solutions. For any fault displayed on the operator that is not listed in the following table, please see the V7 Technical Manual.

Table 1.9 – Drive Faults

Fault

Content

Cause

Solution

BUS Option

Com

Error

Communication is not established
between PROFIBUS-DP Master and
the drive.

• Check PROFIBUS-DP communication LED display.

EF0

External Fault from Option

External fault is active from
PROFIBUS-DP option.

• Turn OFF external fault input.

F06

Option Connection Fault

The drive and communication are not
correctly connected.

• Turn OFF the drive power supply and check the connection

of the option unit and drive, and then, turn ON the drive
power supply. If the fault persists, change the option unit.

F21

Communication Option Self-
diagnostic Fault

F22

Com Option Model Code No.
Fault

F23

Com Option Mutual Diagnostic
Fault

Communication option is not working.

• Turn the drive power supply back ON. If the fault persists,

replace the option unit.