Fast i/o input data, Network communications 3-11 – Yaskawa V7 PROFIBUS-DP User Manual

Page 39

Advertising
background image

Network Communications 3-11

‹ Fast I/O Input Data

This area is used to transfer parameter data directly from the drive dual port RAM interface. The following tables detail the functions of
the fast I/O input data (Bytes 0 to 5)

Table 3.14 – 3 Word Message Fast I/O Input Data

Fast I/O Input Data (V7 -> PROFIBUS-DP Master )

Byte

Function

Bit

Note

0 Running

1 @

Zero

Speed

2 @

Reverse

3 Reset

Signal

4 @

Frequency

Agree

5

Drive Ready (Rdy)

6 Minor

Fault

0

7 Major

Fault

8 OPE

Error

9 Fault

Restart

10 Local/Remote

11

Multi-function Output 1

1 = Close (terminal function dependent on setting of parameter n057)

12

Multi-function Output 2

1 = Close (terminal function dependent on setting of parameter n058)

13

Multi-function Output 3

1 = Close (terminal function dependent on setting of parameter n059)

14 Reserved

1

Drive

Status

15 Reserved

2

Frequency Reference MSB

3

Frequency
Reference

Frequency Reference LSB

0.01Hz
scaling is dependent on the setting of parameter n035

4 Torque

Reference

MSB

5

Torque
Reference

Torque Reference LSB

0 – 100%