16 word input/output message, Network communications 3-3 – Yaskawa V7 PROFIBUS-DP User Manual

Page 31

Advertising
background image

Network Communications 3-3

16 Word Input/Output Message

The V7 PROFIBUS-DP Option can be configured as one of three possible I/O configurations; 16 word input/output message, 6 word
input/output message and 3 word I/Os, combined input/output, messages. The 16 word input/output message structure is described in this
section.

The 16 word input and output messages are divided into two areas. The first 16 bytes of each message is fixed. This is the most frequently
used data and is referred to as the fast I/O data. The remaining 16 bytes of each message are used for reading from and writing to all other
drive parameters and is referred to as parameter data. All command, monitor, and parameter data in the drive is accessible via the
Parameter Access portion of the message.

Table 3.1 – V7 PROFIBUS-DP 16 Word Input/Output Message Table

Output Data (PROFIBUS-DP Master-> V7)

Input Data (V7 -> PROFIBUS-DP Master )

Byte

Function

Byte

Function

0

RUN Operation Command MSB

0

Drive Status MSB

1

RUN Operation Command LSB

1

Drive Status LSB

2

Frequency Reference MSB

2

Reserved

3

Frequency Reference LSB

3

Reserved

4 Reserved

4 Reserved

5 Reserved

5 Reserved

6 Reserved

6 Reserved

7 Reserved

7 Reserved

8

Reserved

8

Frequency Reference MSB

9

Reserved

9

Frequency Reference LSB

10 Reserved

10 Output

Frequency

MSB

11 Reserved

11 Output

Frequency

LSB

12

Reserved

12

Output Current MSB

13

Reserved

13

Output Current LSB

14

Multifunction Digital Output MSB

14

Main Speed Pulse Train Command MSB

Fast I/

O

Area

15

Multifunction Digital Output LSB

Fast I/

O

Area

15

Main Speed Pulse Train Command LSB

16

Function Code

16

Function Code

17

Starting Address MSB

17

Starting Address MSB

18

Starting Address LSB

18

Starting Address LSB

19

Data Length (2, 4, 6 or 8 bytes of data)

19

Data Length (2, 4, 6 or 8 bytes of data)

20

Data 1 MSB

20

Data 1 MSB

21

Data 1 LSB

21

Data 1 LSB

22

Data 2 MSB

22

Data 2 MSB

23

Data 2 LSB

23

Data 2 LSB

24

Data 3 MSB

24

Data 3 MSB

25

Data 3 LSB

25

Data 3 LSB

26

Data 4 MSB

26

Data 4 MSB

27

Data 4 LSB

27

Data 4 LSB

28 Reserved

28 Reserved

29 Reserved

29 Reserved

30 Reserved

30 Reserved

Parameter Acc

e

ss Area

31 Handshake

Register

Parameter Acc

e

ss

Area

31 Handshake

Register