Network Configuration 2-6

GSD File

The listing of the current GSD file is shown below. The GSD file name is YASK00CA.GSD. The file is listed for information purposes only. Do not attempt to
modify the GSD file in any way.

;=====================================================================
; Device description file according to DIN 19245 Part 3 (PROFIBUS-DP)
;=====================================================================
;; FILENAME : YASK00CA_Rev1YEA.GSD
;---------------------------------------------------------------------
; DEVICENAME : PROFIBUS-DP INTERFACE CARD SI-P1
;---------------------------------------------------------------------
; PROTOCOL : PROFIBUS-DP slave
;---------------------------------------------------------------------
; VENDOR : Yaskawa Electric

;---------------------------------------------------------------------
; DATE : 06 June 2001
;---------------------------------------------------------------------
; MODIFICATIONS : 06 June 2001, rev. 3.0 Created
;

08 April 2002, TW,rev 3.3 Revised for customer compatibility

;;=====================================================================

#PROFIBUS_DP
GSD_Revision = 1
Vendor_Name = "YASKAWA ELECTRIC"
Model_Name = "PROFIBUS-DP INTERFACE CARD SI-P1"
Revision = "Version 3.3"
Ident_Number = 0x00CA
Protocol_Ident = 0
Station_Type = 0
FMS_supp = 0
Hardware_Release = "Version 1.3"
Software_Release = "Version 3.3"
9.6_supp = 1
19.2_supp = 1
45.45_supp = 1
93.75_supp = 1
187.5_supp = 1
500_supp = 1
1.5M_supp = 1
3M_supp = 1
6M_supp = 1
12M_supp = 1
MaxTsdr_9.6 = 60
MaxTsdr_19.2 = 60
MaxTsdr_45.45 = 250
MaxTsdr_93.75 = 60
MaxTsdr_187.5 = 60
MaxTsdr_500 = 100
MaxTsdr_1.5M = 150
MaxTsdr_3M = 250
MaxTsdr_6M = 450
MaxTsdr_12M = 800
Redundancy = 0
Repeater_Ctrl_Sig = 2
24V_Pins = 0
Implementation_Type = "SPC3"
Freeze_Mode_supp = 1
Sync_Mode_supp = 1
Auto_Baud_supp = 1
Set_Slave_Add_supp = 0
Min_Slave_Intervall = 1
Modular_Station = 1
Max_Module = 1
Max_Input_Len = 32
Max_Output_Len = 32
Max_Data_Len = 64
Modul_Offset = 1
Fail_Safe = 0
Slave_Family = 1
Max_Diag_Data_Len = 6
Module = "Basic data" 0x72
EndModule
Module = "Extended Data 1" 0x5F, 0x6F
EndModule
Module = "Extended Data 2" 0x55, 0x65
EndModule