Fast i/o output data, Network communications 3-4 – Yaskawa V7 PROFIBUS-DP User Manual
Page 32

Network Communications 3-4
Fast I/O Output Data
The fast I/O output data area is used to transfer parameter data directly to the drive via a dual port RAM interface. The following table
details the functions of the fast I/O output data (Bytes 0 to 15) For detailed explanation of the terminal and multi-function inputs and
outputs, refer to the V7 Technical Manual.
Table 3.2 – 16 Word Input/Output Message Fast I/O Output Data
Fast I/O Output Data (PROFIBUS-DP Master -> V7)
Byte
Function
Bit
Note
0
Fwd Run/Stop
1 = RUN Forward (Enabled when n003 is set to 3)
1
Rev Run/Stop
1 = RUN Reverse (Enabled when n003 is set to 3)
2
Terminal S3
1 = Close (terminal function dependent on setting of parameter n052)
3
Terminal S4
1 = Close (terminal function dependent on setting of parameter n053)
4
Terminal S5
1 = Close (terminal function dependent on setting of parameter n054)
5
Terminal S6
1 = Close (terminal function dependent on setting of parameter n055)
6
Terminal S7
1 = Close (terminal function dependent on setting of parameter n056)
0
7 Reserved
8
External Fault
1 = External Error
9
Fault Reset
1 = Reset Fault
1
Command
Reference
Ah - Fh
Reserved
2
Frequency Reference MSB
3
Frequency
Reference
Frequency Reference LS
0.01Hz
scaling is dependent on the setting of parameter n035
4 - 13
Reserved
Must be set 0
0
Terminal MA MB MC
1 = Close (terminal function dependent on setting of parameter n057)
1
Terminal P1-PC
1 = Close (terminal function dependent on setting of parameter n058)
2
Terminal P2-PC
1 = Close (terminal function dependent on setting of parameter n059)
14
Multi-Function
Output
3 - Fh
Reserved
15
Reserved