‹ Fast I/O Output Data

The fast I/O output data area is used to transfer parameter data directly to the drive via a dual port RAM interface. The following table
details the functions of the fast I/O output data (Bytes 0 to 15) For detailed explanation of the terminal and multi-function inputs and
outputs, refer to the V7 Technical Manual.

Table 3.2 – 16 Word Input/Output Message Fast I/O Output Data

Fast I/O Output Data (PROFIBUS-DP Master -> V7)

Byte

Function

Bit

Note

0

Fwd Run/Stop

1 = RUN Forward (Enabled when n003 is set to 3)

1

Rev Run/Stop

1 = RUN Reverse (Enabled when n003 is set to 3)

2

Terminal S3

1 = Close (terminal function dependent on setting of parameter n052)

3

Terminal S4

1 = Close (terminal function dependent on setting of parameter n053)

4

Terminal S5

1 = Close (terminal function dependent on setting of parameter n054)

5

Terminal S6

1 = Close (terminal function dependent on setting of parameter n055)

6

Terminal S7

1 = Close (terminal function dependent on setting of parameter n056)

0

7 Reserved

8

External Fault

1 = External Error

9

Fault Reset

1 = Reset Fault

1

Command

Reference

Ah - Fh

Reserved

2

Frequency Reference MSB

3

Frequency
Reference

Frequency Reference LS

0.01Hz
scaling is dependent on the setting of parameter n035

4 - 13

Reserved

Must be set 0

0

Terminal MA MB MC

1 = Close (terminal function dependent on setting of parameter n057)

1

Terminal P1-PC

1 = Close (terminal function dependent on setting of parameter n058)

2

Terminal P2-PC

1 = Close (terminal function dependent on setting of parameter n059)

14

Multi-Function
Output

3 - Fh

Reserved

15

Reserved