Installation 1-10

‹ Verify V7 PROFIBUS-DP Option Operation

„ Apply power to the drive.

„ Verify that the diagnostic LEDs on the front of the V7 PROFIBUS-DP Option are in their correct state.

Table 1.4 – Correct Diagnostic LED States

LED Display

PWR

COM

ERR

WD

Content

Cause

Solid Green

Solid Green

OFF

Flashing Green

Normal

Normal communication possible.

„ Remove power from the drive and wait for the charge lamp to be completely extinguished. Wait at least five additional minutes

for the drive to be completely discharged. Measure the DC bus voltage and verify that it is at a safe level.

„ Secure the communication option to the drive, aligning the recessed screw at the top-center of the option with the threaded hole

in the mounting bracket.

„ Install the operator keypad and terminal cover.

„ Set drive parameters n003, n004 and n035 to appropriate values.

Table 1.5 – Option Specific Parameter Settings

Addr

Param

Function

Data

+/- Limits - Description

Default

0 Operator

keypad

1 Terminal

2 Serial

Communication

103h n003

Operation

Method

Selection

3

Option Card (PROFIBUS-DP Option)

1

0

Operator keypad Pot

1

Operator keypad

2 Voltage

Reference

(0-10v)

3

Current Reference (4-20 Ma)

4

Current Reference (0-20 Ma)

5

Pulse Train Reference

6 Serial

Communication

7 Multi-Function

Analog Input (0-10vdc)

8 Multi-Function

Analog

Input(4-20ma)

104h n004

Reference

Selection

9

Option Card (PROFIBUS-DP Option)

2

0

0.01 Hz (< 100hz), 0.1hz (100 Hz >=100hz)

1 0.1%

2-39 Rpm

123h

n035

Frequency Reference Unit Selection

40-3999 User

Setting

0