3 - 22

3. SIGNALS AND WIRING

(2) Torque limit

(a) Torque limit and generated torque

By setting parameter No. 28 (internal torque limit 1), torque is always limited to the maximum
value during operation. A relationship between the limit value and servo motor-generated torque is
shown below.

0

0

100

Max. torque

G

enera

ted t

o

rque

Torque limit value [%]

A relationship between the applied voltage of the analog torque limit (TLA) and the torque limit
value of the servo motor is shown below. Generated torque limit values will vary about 5% relative
to the voltage depending on products.
At the voltage of less than 0.05V, generated torque may vary as it may not be limited sufficiently.
Therefore, use this function at the voltage of 0.05V or more.

2k

1k

Servo amplifier

Japan Resistor
RRS10 or equivalent

TL

SG

P15R

TLA

LG

SD

100

0

0

10

±

5%

0.05

To

rque l

im

it

val

ue

[%

]

TLA application voltage vs.

torque limit value

TLA application voltage [V]