5 - 6

5. PARAMETERS

Class

No.

Symbol

Name and Function

Initial

Value

Unit

Setting

Range

Control

Mode

5

INP

In-position range:

Used to set the droop pulse range in which the imposition (INP)
signal will be output.

100

pulse

0

to

10000

P

6

PG1

Position loop gain 1:

Used to set the gain of position loop 1.
Increase the gain to improve trackability in response to the position
command.

145

red/s

4

to

1000

P

7

PST

Position command acceleration/deceleration time constant
(smoothing):

Used to set the time constant of a low pass filter in response to the
position command.
Example: When a command is given from a synchronizing detector,
synchronous operation can be started smoothly if started during line
operation.

Synchronizing
detector

Start

Servo amplifier

Servo motor

Without time
constant setting

Servo motor

speed

Start

With time
constant setting

ON
OFF

t

3

ms

0

to

20000

P

Internal speed command 1:

Used to set speed 1 of internal speed commands.

S

8

SC1

Internal speed limit 1:

Used to set speed 1 of internal speed limits.

100

r/min

0 to

instan-

taneous

permi-

ssible
speed

T

Internal speed command 2:

Used to set speed 2 of internal speed commands.

S

B

asi

c p

ara

meters

9

SC2

Internal speed limit 2:

Used to set speed 2 of internal speed limits.

500

r/min

0 to

instan-

taneous

permi-

ssible
speed

T