3 torque control mode, Troubleshooting – MITSUBISHI ELECTRIC J2-JRSERIES MR-J2-03A5 User Manual

Page 129

Advertising
background image

9 - 5

9. TROUBLESHOOTING

9.1.3

Torque control mode

No.

Start-Up Sequence

Fault

Investigation

Possible Cause

Refer To

Not improved if connectors
CN1A, CN1B and CNP2 are
disconnected.

1. Power supply voltage fault
2. Servo amplifier is faulty.

Improved when connectors
CN1A and CN1B are
disconnected.

Power supply of CN1 cabling is
shorted.

x

LED is not lit.

x

LED flickers.

Improved when connector
CNP2 is disconnected.

1. Power supply of encoder

cabling is shorted.

2. Encoder is faulty.

1

Power on

Alarm occurs.

Refer to Section 9.2 and remove cause.

Section 9.2

Alarm occurs.

Refer to Section 9.2 and remove cause.

Section 9.2

2

Switch on servo-on
signal.

Servo motor shaft is
not servo-locked
(is free).

Check the display to see if
the servo amplifier is ready
to operate.

1. Servo on signal is not input.

(Wiring mistake)

2. 24VDC power is not

supplied to COM.

Section 6.3

Call the status display and
check the analog torque
command.

Analog torque command is 0V.

Section 6.2

Call the external I/O signal
display and check the
ON/OFF status of the input
signal.

RS1 or RS2 is off.

Section 6.6

Check the internal speed
limits 1 to 3
(parameters No. 8 to 10).

Set value is 0.

3

Switch on forward
rotation start (RS1)
or reverse rotation
start (RS2).

Servo motor does
not rotate.

Check the internal torque
limit 1 (parameter No. 28).

Set value is 0.

(1),

Section 5.1.2