3 - 41

3. SIGNALS AND WIRING

3.7.2

Explanation of signals

Abbreviation

Signal Name

Description

P24M

Main circuit power input

Power supply for main circuit

P24G

Power ground

Main circuit power supply and control power supply. Connected to SG and LG
inside the unit.

P24L

Control power input

Control power supply and digital I/O power supply. Always use a stabilizing
power supply.

Ground

Grounding terminal
Connect to the earth of the control box for grounding.

3.7.3

Power-on sequence

(1) Power-on procedure

1) Always wire the power supply as shown in above Section 3.7.1 using the relay with the main

circuit power supply. Configure up an external sequence to switch off the relay as soon as an
alarm occurs.

2) Switch on the control circuit power supply P24L, P24G simultaneously with the main circuit

power supply or before switching on the main circuit power supply. If the main circuit power
supply is not on, the display shows the corresponding warning. However, by switching on the
main circuit power supply, the warning disappears and the servo amplifier will operate properly.

3) The servo amplifier can accept the servo-on signal (SON) about 1 second after the main circuit

power supply is switched on. Therefore, when SON is switched on simultaneously with the 24V
power supply, the base circuit will switch on in about 1 second, and the ready signal (RD) will
switch on in further about 20ms, making the servo amplifier ready to operate.

(2) Timing chart

ON

OFF

ON

OFF

ON

OFF

ON

OFF

Power supply

Base circuit

Reset

(RES)

Ready

(RD)

ON

OFF

Servo on

(SON)

SON accepted

(1s)

10ms

20ms

10ms

60ms

60ms

10ms

20ms

10ms

20ms

10ms