System initialization, 1 all clear, except len0000 cat, 2 resident system program – NEC NEAX2000 IVS ND-45492 User Manual

Page 168: Nap 200-010, System initialization and system data entry, Nap- 200-010

Advertising
background image

ND-45492 (E)

CHAPTER 3

Page 151

Revision 2.0

1. System Initialization

There are two methods for System Initialization. The first method is to Clear All Data, except LEN0000 as
a CAT terminal, and then program the System Data. The second method is to use the Resident System Pro-
gram, which causes the system to configure itself automatically to the default settings, wherever the line/
trunk cards are installed. Refer to the System Data Sheet, for the default settings.

Turn on the “SW1” switch on all the PZ-PW86 units.

The “ON” lamp must be lit on all the PZ-PW86 units.

1.1. All Clear, Except LEN0000 CAT

STEP 1:

On the MP Card, set SW3 to “B” and press SW1.

STEP 2:

When the “MN” lamp on the system is lit, set SW3 to the “0” position and press SW1.

The operating mode has been changed to the ON LINE mode.

Note:

Refer to the Circuit Card Manual for information on switch settings.

1.2. Resident System Program

STEP 1:

Mount the Line/Trunk cards into PIM.

STEP 2:

On the MP Card, set SW3 to “C” and press SW1.

After 30 to 40 seconds, the “MN” lamp turns on.

The system has loaded the Resident System Program.

Note:

If the “MJ” lamp is lit, repeat Step 2.

STEP 1:

Set SW3 to the “0” position and press SW1.

The operating mode has been changed to the ON LINE mode.

Note:

Refer to the System Data Sheet for additional information on the Resident System Program and the initial-
ization of the system without a MAT (enabling CAT mode).

NAP 200-010

Sheet 1/3

System Initialization and System Data
Entry

ATTENTION

Contents
Static Sensitive
Handling
Precautions Required