A series – GE Industrial Solutions A Series Lighting Control Panelboards Modbus Register Map User Manual

Page 10

Advertising
background image

A Series

®

Lighting Controller Modbus Register Map

Introduction

4

Object

Quantity

Comments

DEV – Device Information

1 per controller

Fixed registers

INPUTS:

MI – Multi-state Input

80 = 16 inputs * 5 Modules

Switch Input Modules.

AI - Analog Input

19 = 3 On-board +

(8 inputs * 2

Modules)

Daylight Optimization Modules.

AV – Analog Variables

16 = 8 inputs * 2 Modules

Daylight Optimization Modules.

OUTPUTS:

BO - Binary Output

66 = Breakers

4 = Special Outputs

BV – Binary Variables

66

1 Light switch per Breaker

Operational Control:

LG - Lighting Group

16

Each controlling up to 33 local

outputs.

SCH – Schedule

16

7 Day schedules - with 16 On/Off times

per day (+ 2 Calendar references)

CAL – Calendar

2

90 Date entries spanning 10 years

CEL - Compact Event Log

1 per controller

1500 timestamp event records

LS – Load Shed

1

66 outputs, 5 shed levels

Table 3. Object types supported by the Lighting Controller.

Object Type

Object ID for MODBUS

AI - Analog Input

0

AO - Analog Output

1

AV - Analog Variable

2

BI - Binary Input

3

BO - Binary Output

4

BV - Binary Variable

5

CAL – Calendar

6

DEV – Device

Information Object

8

CO – Control Loop

12

MI – Multi-state Input

13

MO – Multi-state Output

14

MV – Multi-state Value

19

SCH – Schedule

17

TL - Trend Log

20

AIC - Analog Input

Configuration

176

BDC - Binary Device

Configuration

178

MIC – Multi-state Input

Configuration

183

LS – Load Shed

182

CEL – Compact Event

Log

297

LNK – LINKnet Device

299

LG - Lighting Group

303

Table 4. Object ID

Advertising