Device properties (editable), A series – GE Industrial Solutions A Series Lighting Control Panelboards Modbus Register Map User Manual

Page 13

Advertising
background image

A Series

®

Lighting Controller Modbus Register Map

Fixed-Value (Device Object) Registers

7

Device Properties (Editable)

Table 9 indicates the editable device properties.

Offset Modbus # reg

Property

Format

Range

Type

0

50001 – 50007 Firmware Version

ASCII

Int (ASCII string)
12 chars max + 2 bytes string size

R

7

50008 – 50014 Hardware Revision

ASCII

Int (ASCII string)
12 chars max + 2 bytes string size

R

14

50015 – 50021 Application software

version

ASCII

Int (ASCII string)
12 chars max

R

21

50022 – 50023 Latitude*

Real

+/- 90.0

R/W

23

50024 – 50025 Longitude**

Real

+/- 180.0

R/W

25

50026

UTC Enable

INT

0 /1

R/W

26

50027

UTC Offset

INT

+/- 32767

R/W

27

50028

DST Enable

INT

0/1

R/W

Last Reset Time/Date

28

50029

Hours/Minutes

WORD

R

29

50030

Seconds/Hundreths sec WORD

R

30

50031

DayOfWeek/Day

WORD

R

31

50032

Month/Year

WORD

R

32

50033

Reset Count

WORD

1 – 65535

R

33

50034

Device Address
(Mac address)

WORD

1 – 99

R

34

50035

Device Control

WORD

1 - Load-from-Flash
2 - Save-to-Flash
3 - Recfg Network

W

Current Time/Date

35

50036

Hours/Minutes

WORD

R/W

36

50037

Seconds/Hundredths
Sec

WORD

R/W

37

50038

DayofWeek/Day

WORD

R/W

38

50039

Month/Year

WORD

R/W

39

50040 – 50046 Product Id

ASCII

INT (ASCII string)
12 chars max + 2 bytes string size

R

Table 9. Types of fixed-value registers.

Note:

Registers of Type R must not be written to even
though the can be viewed with Function 3.

Registers of Type R/W are designed to be
editable. This allows setting the DST/UTC &
Location.

Changing the Current time requires a single write
to registers 50035 to 50038, using Function 16