A series – GE Industrial Solutions A Series Lighting Control Panelboards Modbus Register Map User Manual

Page 40

Advertising
background image

A Series

®

Lighting Controller Modbus Register Map

Schedule Objects

34

Request

Response

Field Name

Hex Field Name

Hex

Device Address

01 Device Address

01

Function

03 Function

03

Register Address Hi

4E Byte Count

40

Register Address Lo

22 Register Value Hi (20003)

00

No. of Registers Hi

00 Register Value Lo (20003) 00

No. of Registers Lo

20 Register Value Hi (20004)

00

Packet CRC Hi

Register Value Lo (20004) 00

Packet CRC Lo

Register Value Hi (20005)

05

Register Value Lo (20005) 00

Register Value Hi (20006)

00

Register Value Lo (20006) 01

Register Value Hi (20007)

06

Register Value Lo (20007) 0F

Register Value Hi (20008)

00

Register Value Lo (20008) 00

Register Value Hi (20009)

07

Register Value Lo (20009) 0F

Register Value Hi (20010)

00

Register Value Lo (20010) 01

Register Value Hi (20011)

09

Register Value Lo (20011) 00

Register Value Hi (20012)

00

Register Value Lo (20012) 00

Register Value Hi (20013)

0A

Register Value Lo (20013) 1E

Register Value Hi (20014)

00

Register Value Lo (20014

01

Register Value Hi (20015)

0C

Register Value Lo (20015) 2D

Register Value Hi (20016)

00

Register Value Hi (20016

00

Register Value Hi (20017)

FF

Register Value Lo (20017) FF

Register Value Hi (20018)

FF

Register Value Lo (20018) FF

Register Value Hi (20019)

FF

Register Value Lo (20019) FF

Register Value Hi (20020)

FF

Register Value Lo (20020) FF

Register Value Hi (20021)

FF

Register Value Lo (20021) FF

Register Value Hi (20022

FF

Register Value Lo (20022) FF

Register Value Hi (20023)

FF

Register Value Lo (20023) FF

Register Value Hi (20024)

FF

Register Value Lo (20024) FF

Register Value Hi (20025)

FF

Register Value Lo (20025) FF

Register Value Hi (20026)

FF

Register Value Lo (20026) FF

Register Value Hi (20027)

FF

Register Value Lo (20027) FF

Request

Response

Field Name

Hex Field Name

Hex

Register Value Hi (20028)

FF

Register Value Lo (20028) FF

Register Value Hi (20029)

FF

Register Value Lo (20029) FF

Register Value Hi (20030)

FF

Register Value Lo (20030) FF

Register Value Hi (20031)

FF

Register Value Lo (20031) FF

Register Value Hi (20032)

FF

Register Value Lo (20032) FF

Register Value Hi (20033)

FF

Register Value Lo (20033) FF

Register Value Hi (20034)

FF

Register Value Lo (20034) FF

Packet CRC Hi

Packet CRC Lo

Table 64. Sample packets for read of schedule day entries.

The response is as follows:

Reg20003–Reg20004 0x0000: 00:00

AM

, 0x0000: Off

time

Reg20005–Reg20006 0x0500: 5:00

AM

, 0x0001” On time

Reg20007–Reg2008 0x060F: 6:15

AM

, 0x0000: Off time

Reg20009–Reg20010 0x070F: 7:15

AM

, 0x0001 – On

time

Reg20011–Reg20012 0x0900: 9:00

AM

, 0x0000: Off time

Reg20013–Reg20014 0x0A1E: 10:30

AM

, 0x0001: On

time

Reg20015–Reg20015 0x0C2D: 12:45

PM

, 0x0000: Off

time


Reg20017–Reg20018 0xFFFF: No entry

Advertising