A series – GE Industrial Solutions A Series Lighting Control Panelboards Modbus Register Map User Manual
Page 33
A Series
®
Lighting Controller Modbus Register Map
Lighting Group Objects
27
by Function Code 06 and 16 and read by Function 3. Write
to LG value is at priority level 1 by default.
Note that any reference in this object that does not exist is
shown as 0xFFFF in all three registers. To delete a
reference, write 0x0000 to all three registers. The same
applies to deleting an entry in any of the two arrays in this
object. Lighting Outputs and Common Group entries are
sorted in object execution time. Therefore, multiple
entries can only be deleted in one write.
The template shown in table 48 is repeated 16 times in
this assigned space.
Register
LG Object
Type
Register
BO Object
Type
4001 – 4363
LG1
RW
6905 – 7267
LG9
RW
4364 – 4726
LG2
RW
7268 – 7630
LG10
RW
4727 – 5089
LG3
RW
7631 – 7993
LG11
RW
5090 – 5452
LG4
RW
7994 – 8356
LG12
RW
5453 – 5815
LG5
RW
8357 – 8719
LG13
RW
5816 – 6179
LG6
RW
8720 – 9082
LG14
RW
6179 – 6542
LG7
RW
9083 – 9445
LG15
RW
6542 – 6904
LG8
RW
9446 – 9808
LG16
RW
Table 47 different lighting group registers
Offset Modbus #regs
DB size
Property
Format
Range
Type
0
4001
BYTE
Out of Service
Int
0 – 1
RW
1
4002
BYTE
Value *
Int
0 – 1
RW
2
4003
BYTE
Current Priority
Int
Enum (1 – 6)
R
3
4004
WORD
Reliability
Int
Enum
R
Override Reference
4
4005
Panel Number
Int
0 – 99
RW
5
4006
Object Type
Int
0 – 65535
BI= 3
BV= 5
RW
6
4007
Object Instance
Word
1 – 65535
RW
7
4008
WORD
Override Time
WORD 0 – 65535
RW
Photocell Reference
8
4009
Panel Number
Word
0 – 99
RW
9
4010
Object Type
Int
0 – 65535
AI= 0
AV= 2
BI= 3
MI= 13
RW
10
4011
Object Instance
Word
1 – 65535
RW
11
4012 – 4013
Photocell On Val WORD
0 – 65535
RW
13
4014 – 4015
Photocell Off Val WORD
0 – 65535
RW
15
4016
Photocell On Enable
Int
On/Off
RW
16
4017
Photocell Off Enable
Int
On/Off
RW
Schedule Reference
17
4018
Panel Number
Int
0 – 99
RW
18
4019
Object Type
Int
0 – 65535
BV= 5
SCH= 17
RW
19
4020
Instance
Word
1 – 65535
RW
20
4021
Schedule Off
Int
On/Off
RW
21
4022
Schedule On
Int
On/Off
RW