A Series

®

Lighting Controller Modbus Register Map

Compact Event Log

43





Modbus reg.

DB size

Property

Format

Range

Type

0

60001- 60002

Byte

Total Events

Int

1 – 2000

R

Alarm Output Ref.

2

60003

Word

Device No

Word

0 - 65535

R

3

60004

Word

Object Type

Word

0 – 65535
BO= 4
BV= 5

R

4

60005

Word

Object Instance

Word

0 – 65535

R

5

60006

Byte

Alarm Ack

Int

0/1

R/W

6

60007- 60008

Byte

Alarm Values

Int

0 - 65535,
0 - 65535

R/W

Table 84. registers to set up alarm events and alarm output reference



*Note: Registers 60001 to 60005 must not be written to even though the can be viewed with Function 3.

Alarm Values Enabled

Reg 60007
(Hexadecimal)

Reg 60008
(Hexadecimal)

None

0000

0000

Lighting Alarms,

0000

0800

Lighting Statuses,

1000

0000

Lighting Alarms, Lighting Statuses,

1000

0800

Time Change

0002

0000

Time Change, Lighting Alarms

0002

0800

Time Change, Lighting Statuses,

1002

0000

Time Change, Lighting Alarms, Lighting Statuses

1002

0800

Device Statuses,

2000

0000

Device Statuses, Lighting Alarms,

2000

0800

Device Statuses, Lighting Statuses,

3000

0000

Device Statuses, Lighting Alarms, Lighting Statuses,

3000

0800

Device Statuses, Time Change

2002

0000

Device Statuses, Time Change, Lighting Alarms

2002

0800

Device Statuses, Time Change, Lighting Statuses,

0800

0000

Device Statuses, Time Change, Lighting Alarms, Lighting Statuses

3002

0800

Table 85. possible register values for every Lighting Alarm Value combination

Alarm Acknowledge: Register 60006 will always display
0000 hex. If the Alarm Relay is active writing 0001 hex
will acknowledge the Alarm. *When alarm is
acknowledged the value of the register will go back to
0000hex.

Alarm Values: Register 60007 – 60008 display the value of
the CEL Alarm Values bit list. Table 85 displays all



possible register values for every Lighting Alarm Value
combination possible in the Compact Event Log.