Physical output registers (coils), A series, Sample packets – GE Industrial Solutions A Series Lighting Control Panelboards Modbus Register Map User Manual

Page 23

Advertising
background image

A Series

®

Lighting Controller Modbus Register Map

Physical Output Registers-Binary Outputs (BO)

17

Physical Output Registers (Coils)

Lighting controller supports up to 66 breaker outputs
(BO). Actual value registers start at 1, commanded by
Function Codes 01, 05, and 15 and are mapped to Binary
Outputs (BO) 1–66. The value in the register represents
the Binary Output’s present value when read. Writes go to
priority level 5. Writes will only be accepted if the
‘OutOfService’ flag is set for that particular output.
A value of 1 represents ON and a value of 0 represents
OFF.
The physical output registers (coils) are listed in Table 26.

Reg.

Contents

Type

Format

BO

Instance

1

BO1 Value

RW

Bit

01

2

BO2 Value

RW

Bit

02

3

BO3 Value

RW

Bit

03

4

BO4 Value

RW

Bit

04

5

BO5 Value

RW

Bit

05

6

BO6 Value

RW

Bit

06

7

BO7 Value

RW

Bit

07

8

BO8 Value

RW

Bit

08

9

BO9 Value

RW

Bit

09

10

BO10 Value

RW

Bit

10

11

BO11 Value

RW

Bit

11

12

BO12 Value

RW

Bit

12

13

BO13 Value

RW

Bit

13

14

BO14 Value

RW

Bit

14

15

BO15 Value

RW

Bit

15

16

BO16 Value

RW

Bit

16

17

BO17 Value

RW

Bit

17

18

BO18 Value

RW

Bit

18

19

BO19 Value

RW

Bit

19

20

BO20 Value

RW

Bit

20

21

BO21 Value

RW

Bit

21

22

BO22 Value

RW

Bit

22

23

BO23 Value

RW

Bit

23

24

BO24 Value

RW

Bit

24

25

BO25 Value

RW

Bit

25

26

BO26 Value

RW

Bit

26

27

BO27 Value

RW

Bit

27

28

BO28 Value

RW

Bit

28

29

BO29 Value

RW

Bit

29

30

BO30 Value

RW

Bit

30

31

BO31 Value

RW

Bit

31

32

BO32 Value

RW

Bit

32

33

BO33 Value

RW

Bit

33

34

BO34 Value

RW

Bit

34

35

BO35 Value

RW

Bit

35

36

BO36 Value

RW

Bit

36

37

BO37 Value

RW

Bit

37

38

BO38 Value

RW

Bit

38

39

BO39 Value

RW

Bit

39

40

BO40 Value

RW

Bit

40

Reg.

Contents

Type

Format

BO

Instance

41

BO41 Value

RW

Bit

41

42

BO42 Value

RW

Bit

42

43

BO43 Value

RW

Bit

43

44

BO44 Value

RW

Bit

44

45

BO45 Value

RW

Bit

45

46

BO46 Value

RW

Bit

46

47

BO47 Value

RW

Bit

47

48

BO48 Value

RW

Bit

48

49

BO49 Value

RW

Bit

49

50

BO50 Value

RW

Bit

50

51

BO51 Value

RW

Bit

51

52

BO52 Value

RW

Bit

52

53

BO53 Value

RW

Bit

53

54

BO54 Value

RW

Bit

54

55

BO55 Value

RW

Bit

55

56

BO56 Value

RW

Bit

56

57

BO57 Value

RW

Bit

57

58

BO58 Value

RW

Bit

58

59

BO59 Value

RW

Bit

59

60

BO60 Value

RW

Bit

60

61

BO61 Value

RW

Bit

61

62

BO62 Value

RW

Bit

62

63

BO63 Value

RW

Bit

63

64

BO64 Value

RW

Bit

64

65

BO65 Value

RW

Bit

65

66

BO66 Value

RW

Bit

66

Table 26. List of physical output registers (coils).

Sample Packets

The following are examples of packets generated by
requests for specific groups of outputs.

Read Coil Status of BO Reg2 to Reg17

Table 27 shows the result of a request to read the coil
status of BO Reg2–Reg17 (Function 1, BO2–17 in map).
Note that the status of outputs 9–2 is shown as the byte
value 0xAC or binary 1010 1100 and output 2 is the LSB.

Request

Response

Field Name

Hex

Field Name

Hex

Device Address

01

Device Address

01

Function

01

Function

01

Register Address Hi

00

Byte Count

02

Register Address Lo

01

Output Status 9–2

AC

Quantity of Outputs Hi

00

Output Status 17–10 0A

Quantity of Outputs Lo

10

Packet CRC Hi

Packet CRC Hi

Packet CRC Lo

Packet CRC Lo

Table 27. Sample packet for coil status of BO Reg2 to Reg17.